Image copyright belongs to the manufacturers or original authors. Brands and models identify illustrations; consult official documentation when selecting parts.
ENGINEERING GUIDE
Selection and design guide
A wiring duct mounts on the mounting plate of an electrical enclosure. Wires enter and leave through the slots on both sides, and the cover keeps them tidy and traceable. Take the OBO LK4 as an example: the nominal size is the internal cavity size, from 15×15 to 80×120 mm in 21 sizes, with side slots 4 mm wide at a 10 mm pitch. The PVC body is rated -5 to 60 °C. Following NFPA 79, Panduit sets the maximum fill at 50% of the internal cross-section. Calculate wire cross-section from outer diameters first, then size the duct at 50%, leaving room for cooling and for separating power and control wiring.
01Construction and how it works
A wiring duct has two parts: the base and the cover. A row of slots is cut in each side wall of the base, with fingers between them that can be broken off. Wires turn out through the slots and go straight to nearby terminals, breakers or relays. The base has mounting holes and is fixed to the mounting plate with nylon rivets or screws. Fit the cover once all wiring is complete.
OBO describes the LK4 as follows: the cover opens easily and snaps firmly shut. The finger roots have preset break points and can be removed without tools. The base also has break points, so wires can be led out along the bottom. The LK4/N has narrowed slot mouths so wires cannot fall out. RCCN describes its fine-tooth duct this way: the interlocking cover does not come loose, the joint is smooth and neither cuts hands nor abrades nearby wires, the outlet openings are low, and assembly and removal are simple.
It solves three problems in cabinet wiring. First, hundreds or thousands of wires are routed and layered without crossing or tangling. Second, opening the cover exposes them for changes or tracing. Third, power and control wiring, and power and signal lines, go in separate ducts. In design it takes up a large area and often determines the size of the mounting plate.
02Types and designation systems
Main Panduit Panduct wiring duct types (from the Panduit selection guide)
The cover cannot be lost; double-sided hinges make changes about 20% faster
DRD
Rail and duct in one
Uses cabinet depth, saving up to about 30% of mounting plate area; carries up to 4 lbs/in
CWD
Corner duct
Uses the side panel, saving up to about 20% of space
Shielded (EMI)
Aluminium foil screen over the fingers of type G
Used with a metal divider (Noise Shield) to reduce noise
FL
No cover, interlocking fingers, adhesive backing
For repeated changes on door panels and AGVs
NE / NNC / TNC
Halogen-free (NNC and TNC are metric); TNC is low-smoke halogen-free
For rail and other applications with high fire requirements
From pages 2, 5 and 6 of the Panduit Wiring Duct Product Selection Guide. For G, F, D, FS, HN, H, HS, NE, CWD and the shielded type, base and cover are ordered separately. DRD, NNC, TNC and MC are supplied together.
OBO wiring duct series (from the OBO Wiring trunking catalogue)
Series
How size is stated
Size range
Remarks
LK4, LK4/N
Nominal = internal cavity size
15×15~80×120 mm, 21 sizes
Metric duct; the /N type has narrowed slot mouths to stop wires falling out
LKV, LKV/N
Nominal = outside size
25×25~100×100 mm, 17 sizes
Dimensions follow the former DIN 43659; often called DIN duct
LK4H
Nominal = outside size
30×30~100×100 mm
Halogen-free
LKV/H
Nominal = outside size
50×37.5~75×125 mm, 8 sizes
Halogen-free
From pages 3, 9 and 10 of the OBO catalogue. For the same designation 40×60, an LK4 has an internal cavity of 40×60 and an outside of 44×63 mm. A duct dimensioned by its outside has a cavity a few millimetres smaller. RCCN HVDR fine-tooth duct is also marked by the outside width and height with cover and base assembled.
Slot dimensions compared
Series
Slot width mm
Finger width mm
Pitch mm
OBO LK4
4
6
10
OBO LKV
7.5
5
12.5
RCCN HVDR (4 mm outlet)
4 (5 in some sizes)
6 (5 in some sizes)
—
RCCN VDR (8 mm outlet)
8~8.5
10~12
—
OBO data from the tooth drawing on page 8 of its catalogue; RCCN data from the specification table on its fine-tooth duct product page (slot width Q, finger width P). A narrow slot passes fewer wires per opening but gives denser outlet positions; a wide slot passes a whole bundle at once.
OBO wiring duct base hole patterns and finger shape. On the left, 1, 2 and 3 are three base hole patterns. 1: two rows of holes, 50 mm between rows. 2: a single row of 4.5×8 mm small holes at 25 mm pitch (78×25=1950). 3: a single row alternating 6.5×14 mm slots and 4.5×8 mm small holes, 25 mm apart. Each length is 2000 mm and the first hole is 25 mm from the end. On the right is the finger shape: LKV pitch 12.5, slot 7.5 and finger 5 mm; LK4 pitch 10, finger 6 and slot 4 mm.Image: OBO, Wiring trunking - Precise measurements and tested quality, catalogue page 8
Materials and temperatures (from makers' catalogues)
Maker / type
Material
Flame rating
Permitted temperature
Panduit G, F, D, FS, MC, H, DRD and others
Lead-free rigid PVC
UL 94 V-0
UL recognised for continuous use at 50 °C; maximum use temperature 60 °C declared to the EU Low Voltage Directive; minimum -5 °C for storage, transport and installation
Panduit NE, NNC
Modified polyphenylene oxide (mPPO), halogen-free
UL 94 V-0
Continuous use at 95 °C, 20% lighter than PVC
Panduit TNC
PPE+HIPS, low-smoke halogen-free
UL 94 V-0
Continuous use at 105 °C
Panduit FL
Polypropylene (PP)
UL 94 V-2
Continuous use at 65 °C
OBO LK4 N 60040
PVC, not halogen-free
Self-extinguishing
-5~60 °C
RCCN HVDR
Low-halogen rigid PVC
UL 94 V-0
Static -40 °C, continuous high temperature up to 70 °C; a 110 °C type is also available
From pages 6 and 8 of the Panduit selection guide, the OBO LK4 N 60040 data sheet and the RCCN fine-tooth duct product page. Panduit warns that halogen-free ducts such as NE, NNC and TNC must not contact cleaners or cutting fluids containing hydrocarbons, ketones, ethers, phenols, amines, acids or petrol; stress cracking can result.
Fill ratio: citing clause 13.5.2 of NFPA 79-2012, Panduit sets the maximum fill of all its ducts at 50% of the internal cross-section. The reason is that wire cross-sections are irregular, cross one another and do not pack tightly, so this is what fits in practice. When calculating the internal area, Panduit subtracts the wall thickness and uses 90% of nominal width × height.
N = (W × H) / (1.75 × D²)
N
Maximum number of wires of one size
W, H
Nominal duct width and height (outside nominal for Panduit), in the same units as D
D
Wire outer diameter including insulation
Derivation on page 4 of the Panduit selection guide: 50% fill = 0.5 × (0.9 × W × H) / (0.785 × D²), which simplifies to the formula above. Example: a 25×25 mm (1×1 in) duct holds 46 wires of 14 AWG THHN with an outer diameter of 0.111 in, about 2.8 mm, according to the table. With mixed wire sizes, use instead the sum of the wire cross-sections ≤ 50% of the usable area.
Panduit fill-capacity tables for duct types D, G, F and FS. The left column gives nominal size (width × height, in inches) and nominal area. The columns on the right give the maximum number of wires at 50% fill for different wire gauges (8 to 24 AWG with THHN, MTW and TFFN insulation, outer diameter in inches in the headings). The same columns cover communication cables (Cat.6A, Cat.6, Cat.5e and 3.0 mm optical cable). Four boxes below explain in order the calculation formula, why 50% is used, why usable area is 90% of nominal area, and why wire cross-section is taken as 0.785·D².Image: Panduit, Wiring Duct Product Selection Guide (FRSG4-SA-ENG, 2024), page 4
Examples of usable area and wire capacity from makers
Maker / model
Size mm
Maker's data
OBO LK4 N 60040
Internal cavity 40×60
Usable area 22.38 cm²
RCCN HVDR2525F
Outside 25×25
10~25 wires of 2.0 mm²
RCCN HVDR4545F
Outside 45×45
60~70 wires of 2.0 mm²
RCCN HVDR4060F
Outside 40×60
100~115 wires of 2.0 mm²
RCCN HVDR6060F
Outside 60×60
120~135 wires of 2.0 mm²
RCCN HVDR8080F
Outside 80×80
240~290 wires of 2.0 mm²
RCCN HVDR100100F
Outside 100×100
300~400 wires of 2.0 mm²
Makers use different bases: OBO gives usable area, RCCN gives a range of wire counts for 2.0 mm² wire, and Panduit gives counts at 50% fill. RCCN does not state a fill ratio for its counts, so still check with wire outer diameters to the 50% principle in design.
04Dimensions, interfaces and mounting space
Take the OBO LK4 N 60040 (order number 6178205) as an example: internal cavity 40 mm wide and 60 mm high; outside 44 mm wide and 63 mm high, cover 46.2 mm wide. Each length is 2000 mm. Side slots are 4 mm wide at a 10 mm pitch. The base uses hole pattern 3: a single row alternating 6.5×14 mm slots and 4.5×8 mm small holes, 25 mm apart, with the first hole 25 mm from the end. Weight is 56 kg/100 m. Permitted temperature is -5 to 60 °C. It is tested to DIN EN 50085-2-3.
OBO LK4 duct cross-section dimensions: a is internal width, h internal height (the nominal size), A outside width, B cover width, and H total height with the cover fitted. The table below lists a, A, B, h and H for 21 sizes from LK4 15015 to LK4 N 80120. For example, the LK4 60040 has a 40, A 44, B 46.2, h 60 and H 63 mm.Image: OBO, Wiring trunking - Precise measurements and tested quality, catalogue page 9
Space required in layout (from the OBO LK4 range)
Model
Internal width × height mm
Outside width A mm
Cover width B mm
Total height H mm
Base hole pattern
LK4 30025
25×30
28.6
31
32.8
3
LK4 40040
40×40
43.6
46.2
43
3
LK4 N 60025
25×60
29
31
63
3
LK4 N 60040
40×60
44
46.2
63
3
LK4 N 60060
60×60
64
66.4
63.2
3
LK4 N 60080
80×60
84.4
87
63.7
1
LK4 N 80080
80×80
84.6
87
83.9
1
LK4 N 80120
120×80
124.8
127.8
84.3
1
From pages 8 and 9 of the OBO catalogue. In an OBO model number the height is written first and the width second: LK4 60040 is 60 high and 40 wide. Widths above 80 mm use two rows of holes (pattern 1), and 15 mm wide duct uses pattern 2. On the mounting plate, allow space from the cover width B, not from the nominal width.
Fixing: OBO duct is fixed to the mounting plate with expanding rivets, using a plastic rivet tool. Spacers can also raise the duct off the plate. Panduit supplies NR1 nylon rivets and TNR installation tools, and some sizes can be ordered with adhesive backing.
Typical layout on the mounting plate: a row of rail-mounted devices with a duct above and below it, wires turning straight from the terminals into the slots. Duct height is normally at least the terminal height of the neighbouring devices; otherwise wires must bend down before entering.
Cooling clearances take priority: the cooling space a component requires must not be taken by the duct. Siemens S7-1200 requires at least 25 mm above and below, and at least 25 mm from the front of the module to the enclosure wall. For drives, power supplies and other heat sources, follow their manuals and place the duct outside those clearances.
Separate power and control ducts: the Siemens S7-1200 manual says low-voltage signal and communication lines must not share a duct with AC power lines or DC lines switched rapidly at high current. Where space is short, Panduit states that screened duct with a metal divider reduces noise by up to 20 dB, equivalent to 152 mm (6 in) of air separation.
Space-saving forms: the Panduit DRD rail-duct comes in three cross-sections, 156.7×54.0, 184.1×79.4 and 209.5×104.8 mm, with the rail mounted directly on the duct. The CWD corner duct comes in 85.0×64.4, 111.8×90.7 and 135.3×115.7 mm, for the corner between the mounting plate and a side panel.
The cover must come off: do not fit other parts tight against the duct above or below it; leave finger space to open the cover. Panduit declares to the EU Low Voltage Directive (EN 50085-1, EN 50085-2-3) that its covers can be removed without tools, provided a hand can reach them.
05Selection steps and calculation
1 List the wires in each ductFrom the electrical drawing, list every wire passing through a given duct run: size, quantity and outer diameter, including insulation, from the wire data sheet. The most crowded run determines the duct size.
2 Calculate the total wire cross-sectionTake each wire as 0.785·D² and add them up. Power cables, encoder cables and network cables differ greatly in outer diameter, so calculate them separately.
3 Size the duct cross-section at 50%Total wire cross-section ≤ 50% of usable area. Use the maker's value where given, for example 22.38 cm² for the OBO LK4 N 60040. If none is given, use the Panduit method of 90% of nominal width × height.
4 Fix the width and heightOnce the area is enough, check the height. Duct height must be at least the terminal height of neighbouring devices, and the width must accommodate cover width B. Ducts wider than 80 mm have two rows of base holes, so allow for them on the plate.
5 Fix the slot typeWith dense devices and one wire per terminal, use narrow slots (LK4 pitch 10 mm, Panduit F). To pass a whole bundle at once, use wide slots (Panduit G, LKV).
6 Fix the materialWhere cabinet temperature exceeds the PVC limit, or halogen-free and fire requirements apply, choose materials such as mPPO or PPE+HIPS (Panduit NE/NNC at 95 °C, TNC at 105 °C; OBO LK4H and LKV/H are halogen-free).
7 Allow a margin50% is an upper limit. Allow extra space for wires added or changed later, or the cover will not close during the first commissioning changes.
Example: the OBO LK4 N 60040 has a usable area of 2238 mm², and 50% of that is 1119 mm². Using only wires of outer diameter 2.8 mm (equivalent to 14 AWG THHN in the Panduit table), each takes 6.2 mm², so about 180 fit. The Panduit formula with nominal 40×60 gives 172. The two methods are close; take the smaller value.
Cutting: cut the duct to the required length with a square, deburred end. Panduit offers bench and handheld duct cutters (PBDCT, DCT), a finger-breaking tool DFCT and an opening tool DNT-100.
Fit the base first and cover after wiring: RCCN instructs you to fix the base, lay the wires in the duct and then fit the cover.
Break fingers for outlets: snap off the finger at the outlet position along its preset break point. Do not cut through the middle with side cutters, which leaves a sharp edge.
Stop wires falling out: both OBO and Panduit supply wire retainers that clip into the slots, so wires stay in place when the cover is opened for changes. The OBO retainer can be broken to suit the slot width, so one size fits all.
Separating power and control: use a divider when they must share one duct. Panduit has PVC, slotted and halogen-free dividers. Under UL 508 section 15, the PVC divider can serve as an insulating barrier.
Protect bend radius at corners: the Panduit corner strip (CSC1LG6) controls a 1 in bend radius and is used at right-angle and T joints, in line with the NFPA 79 requirement for cable bend radius.
Do not fit in the cold: Panduit states a minimum storage, transport and installation temperature of -5 °C, and the OBO LK4 has the same lower limit. Fitting cabinets outdoors or in a cold store in winter makes PVC fingers brittle.
07Failure modes and maintenance
Common problems
Symptom
Possible cause
Action
Cover will not close or springs open
Fill above 50%, with no margin for changes
Recalculate at 50%; use the next size up or split into two ducts
Fingers break and the base cracks
Installed below -5 °C; prised open by a wire bundle
Install at normal temperature; break fingers at the preset points for outlets
Duct deforms and yellows
Near a heat source such as a brake resistor or transformer, above the material's temperature
Move the heat source or use a higher-temperature material (95~105 °C grade)
Halogen-free duct cracks
Contact with cleaners or cutting fluids containing ketones or hydrocarbons
Avoid them per the Panduit chemical list, or change to the PVC type
Signal interference
Signal and power wires in the same duct
Route in separate ducts, or add screened duct and a metal divider
Wires scatter when changes are made
No wire retainers fitted
Add wire retainers at the slots
Compiled from the Panduit selection guide and the OBO catalogue.
Maintenance: after changes, check that fill is still within 50%. Do not force new wires under the cover and close it anyway. Replace a damaged cover on its own; for Panduit types G, F, D and FS the covers are ordered separately.
08Common design mistakes
Allocating space by the nominal size: the LK4 60040 has a cover width of 46.2 mm, not 40 mm. With seven or eight ducts on one plate, the error adds up to tens of millimetres.
Confusing internal and outside dimensioning: OBO LK4 is dimensioned by the internal cavity, while LKV, LK4H and RCCN HVDR use the outside. Both may be called 40×60, but they hold different amounts of wire.
Estimating by wire count instead of outer diameter: power, servo and network cables differ several times in diameter, so a count-based estimate often will not fit.
Allowing no margin for changes: fill to 50% at the first build and the cover will not close as soon as a wire is added at commissioning.
Letting duct take up cooling clearance: the upper and lower clearance a component's manual requires, such as 25 mm for the S7-1200, is occupied by the duct, and the cabinet overheats locally.
Power and signal wires in the same duct: drive output cables and brake cables mixed with encoder and analogue lines make interference hard to trace.
Using ordinary PVC duct in a hot cabinet: Panduit PVC is UL recognised only for continuous use at 50 °C and the OBO LK4 limit is 60 °C. Above that, use a halogen-free high-temperature material.
09Standards and manufacturer ranges
Standards cited in the sources
Standard
Subject
Source
EN 50085-1, EN 50085-2-3
Cable trunking systems; slotted duct for mounting inside enclosures
Panduit selection guide; OBO catalogue
DIN 43659
Dimensions, base hole patterns, slot sizes and pitches of slotted duct for switchgear
Panduit selection guide; OBO catalogue
UL 1565, CSA C22.2 No. 18.5
Flame rating V-0 and continuous use temperature of duct material
Panduit selection guide
NFPA 79-2012 clause 13.5.2
Duct fill ratio; Panduit sets 50% from it
Panduit selection guide
NFPA 79-2012 clause 13.3.1
Non-metallic duct in enclosures must be flame-retardant (tested to IEC 60332-1)
Panduit selection guide
NFPA 79-2012 clause 13.1.6.9
Cable bend radius control
Panduit selection guide
UL 508 section 15
Material for insulating dividers
Panduit selection guide
EN 45545-2
Fire protection in rail vehicles (NNC and TNC types)
Panduit selection guide
GB/T 5226.1 (corresponding to IEC 60204-1)
General requirements for electrical equipment of machines
Basis for electrical design
Current editions apply. Electrical design and wiring are done by qualified electricians to GB/T 5226.1 and similar standards. The fill ratios and clearances here are only calculation methods for mechanical layout.
Panduit: Panduct G, F, D, FS, MC, H/HN/HS, DRD, CWD, the shielded type, FL and NE/NNC/TNC.
OBO Bettermann: LK4, LK4/N, LKV, LKV/N, LK4H and LKV/H, all to EN 50085-2-3, UL file E301798.
RCCN: HVDR (4 mm outlets) and VDR (8 mm outlets) fine-tooth duct, UL E306674, standard length 2 m.
Phoenix Contact, Rittal and Hager also offer similar products; their catalogues govern the data.
Tables and formulas are rearranged from the sources above. Verify against the current standard and the manufacturer catalogue before finalising a design. Updated 2026-11-22
ONLY ON MECHWIKI / SELECT · BUY · MAINTAIN
Buying and using: calculators, sellers, uses
The notes below cover the “Relays, wiring & enclosures” category. MechWiki prepared these category notes from public standards and engineering references. Use the selected manufacturer’s catalog for ratings, life factors and dimensions.
07 / SELLERS
Who sells it
The directory links to manufacturer selection and CAD resources and identifies the maker of the pictured example. Check stock and lead time with the supplier. Price comparison and ranking are not available yet.
Schneider ElectricElectrical, industrial control and energy-management products and support.
Layered routing and separation of wire bundles in distribution and control cabinets, keeping conductors from crossing and tangling.
Control cabinet (door and mounting panel)Schematic, not to scaleArrow: Relays & terminals
Isolation and amplification between PLC outputs and loadsTransition between cabinet and field cablingMounting and protection of machine electrical componentsField push-button and junction boxes