A control component monitoring safety inputs and producing corresponding safety outputs.
02 / CONSTRUCTION
Construction & recognition
Normally incorporates diagnostic and redundancy-related features. Configuration must match input devices, circuit structure and application requirements.
03 / APPLICATIONS
Common applications
Emergency-stop, guard-door and safety-light-curtain circuits.
Image copyright belongs to the manufacturers or original authors. Brands and models identify illustrations; consult official documentation when selecting parts.
ENGINEERING GUIDE
Selection and design guide
A safety logic unit that takes safety inputs such as emergency stops, door switches and light curtains, and drops the contactors through forcibly guided contacts and two-channel redundancy. Selection covers the input type (contact or OSSD), the number of channels, the reset mode, the feedback loop and whether a delayed drop-out is needed. It also covers the wiring under which the maker's declared PL and category were obtained.
01Construction and how it works
An ordinary interface relay fails in an uncertain way. If a contact welds and the coil is then de-energised, the contact stays closed, the machine stays live and the controller does not know. A safety relay (safety relay unit) exists to solve this. Inside it uses two or more forcibly guided contact relays (Omron calls them forcibly guided contacts, e.g. the G7SA series, to EN 50205 class A). On one relay the normally open and normally closed contacts move together mechanically, so a welded normally open contact keeps the normally closed contact from closing again. Before every start the unit checks that these normally closed contacts have all reset; if not, it withholds the output.
Two-channel redundancy: the two normally closed contacts of an emergency stop or door switch go to two separate channels (T11-T12 and T21-T22 on the G9SA), and an opening in either channel drops the output.
Cross monitoring: the G9SA contains positive temperature coefficient thermistors that detect a short of an input line to earth or between channels. On detection it cuts the safety output, and it recovers automatically once the fault is cleared.
Both channels must reset: on the G9SA an opening of channel 1 alone also drops the output. To restart, both channels must open and then close; resetting channel 1 alone will not do.
Feedback loop (EDM, external device monitoring): the normally closed auxiliary contacts of the two downstream contactors go in series into the feedback terminals (T31-T32 on the G9SA). If either contactor sticks, the feedback loop is open and the safety output can no longer be switched ON.
Outputs: the G9SA has 3 or 5 pairs of normally open safety contacts and 1 pair of normally closed auxiliary contacts; the auxiliary contacts must not be used in a safety circuit.
Typical wiring for a two-channel emergency stop input with manual reset (Omron G9SA-301 example). S1 is an emergency stop button with a direct opening action, its two normally closed contacts 11-12 and 21-22 going to the two channels. S2 is the reset switch. KM1 and KM2 are the two contactors, whose normally closed auxiliary contacts form the feedback loop back to the unit. KM3 is a solid state contactor, and the PLC is used for monitoring only (PLC input/output), not in the safety circuit. The timing chart on the right shows the sequence: emergency stop pressed, K1 and K2 open, KM1 and KM2 open, motor M stops; after the emergency stop is released, the reset switch S2 must be pressed once more before the machine restarts. The maker's assessment of this example is PLe / category 4 equivalent, stop category 0Image: Omron (OMRON) data sheet Safety Relay Unit G9SA, Application Examples
02Types and designation systems
Common types of safety relay (Omron product line example)
Type
Use
Example series
For emergency stop and door switches (contact input)
1-channel or 2-channel normally closed contact input
G9SA-301/501, G9SB-2002/2031, G9SE
For OSSD input
Takes the transistor safety outputs of light curtains, scanners and the like
G9SB-200-B/D, G9SB-301-B/D; the G9SA-301 also takes PNP light curtains
Delayed drop-out type
Instantaneous contacts open first and delayed contacts later, for stop category 1
G9SA-321-T□ (0.5~30 s), G9SA-EX031-T□ expansion unit, G9SX delay unit (up to 150 s)
Two-hand controller
Output only when both buttons are pressed together
G9SA-TH301
Dedicated function unit
Standstill detection, low speed monitoring, non-contact door switch controller
G9SX standstill detection unit (back EMF detection), G9SX-LM, G9SX-NS
Expansion unit
Adds safety contacts
G9SA-EX301
Programmable safety controller
Many inputs, and logic such as zone stopping or muting
G9SP, NX-SL5 safety CPU
Compiled from the Omron Safety Relay Unit G9SA data sheet, the Safety Relays product presentation and the Safety Components Selection Guide (Y228).
Reset modes
Mode
Behaviour
Where used
Manual reset
After the input recovers, the reset button must still be pressed for the output to go ON
Emergency stops, and areas a person can enter and stay in; mount the reset button where the whole danger zone is visible
Automatic reset
The output goes ON as soon as the input recovers
Only where the machine has a separate start button, or where no one can stay in the danger zone
Monitored reset
Checks the action of the reset button (for example release after press), to guard against a jammed reset button
The exact logic is per the catalogue
The G9SA switches between manual and automatic reset with terminals A and B (data sheet page 5). The Rockwell MatGuard installation instructions point out that with automatic reset the machine control system needs a separate reset function. Otherwise the machine may restart by itself after a person steps off the mat or after a brief power dip.
Stop categories
Category
Meaning
Example in the sources
0
Power to the actuators is cut at once (uncontrolled stop)
G9SA-301 emergency stop and door switch example: the switch acts and the contactors drop
1
A stop is commanded first and power is cut after a delay (controlled stop)
G9SA-321-T□ example: with the door open the motor controller slows the motor first, and the motor supply is cut when the delay expires
2
Supply is kept on after the controlled stop
No example in the maker material cited here; design from the text of IEC 60204-1 and the drive documentation
The first two rows are from the application examples in the Omron G9SA data sheet (pages 7~12).
03Key parameters
Main G9SA specifications (example)
Item
Value
Supply
AC/DC 24 V or AC 100~240 V, 85%~110% of rated voltage
Contact rating
AC 250 V 5 A, DC 30 V 5 A (resistive); reduced to 3 A when several units are mounted close together
Operating time
≤30 ms (excluding bounce)
Response time
≤10 ms (input OFF to the main contacts opening, including bounce)
Life
Mechanical 5 million operations or more; electrical 100,000 operations or more (about 1800 operations/h)
Omron Safety Relay Unit G9SA data sheet, pages 1~3 and 16.
Response time enters the safety distance. The total time from the light curtain or door switch to the contactors opening = input device response time + safety relay response time + contactor release time + machine stopping time. The safety distance formula is in the safety light curtain article.
The level is the level of an example. The G9SA catalogue states that wiring as in the example Omron gives meets PLe / category 4, and that some conditions of use may not reach it. The delayed outputs (G9SA-321-T□, EX031-T□) reach only PLd / category 3. The applicable level is decided by the whole safety control system.
04Selection and calculation
List the safety functionsFor each emergency stop, door and light curtain, set out which hazardous motions it guards, whether the stop category is 0 or 1, and the required PL from the risk assessment.
Fix the input typeContact input types suit mechanical contacts: emergency stops, door switches and pull ropes. For OSSD inputs such as light curtains choose the matching model, and check that voltage, current and test pulses are compatible.
Fix the number of channels and the reset modeA high level generally takes two channels; where a person can enter the danger zone, use manual reset.
Fix the number of output contacts and the loadCount the contactors to be dropped and the signals needed for PLC monitoring; add an expansion unit if they exceed the outputs. Check the contact rating and the derating for several units mounted close together.
Decide on a delayWhere the motor must slow down before the supply is cut (stop category 1), choose the delayed type with a delay longer than the slowing time.
Safety relay or safety controllerFor one or two safety functions with simple logic, use a safety relay. For many inputs, or zone stopping, muting and mode changeover, use a safety controller such as the G9SP, or a controller with a safety CPU.
Contactors and feedbackTwo contactors in series break the main circuit. Choose contactors with forcibly guided (mirror) auxiliary contacts, and put the normally closed auxiliary contacts in series in the feedback loop.
05Installation, adjustment and use
One switch to one unit: the G9SA requires that several units must not share the same switch contact for their inputs.
A slow supply rise gives an error: if the supply takes long to come up while the input is already closed, the G9SA treats the voltage as abnormal and does not work. Let the voltage reach its rated value before energising the unit.
Put the suppressor across the load: the suppressor of an inductive load goes across the coil, not across the contacts. A diode slows the release of the contactor, so measure the response time with it fitted.
Replace the relay on count: the life of forcibly guided contacts depends on the switching conditions. Operations beyond the permitted number lead to reset failure, and further use loses the safety function, so replace the relay at once.
Leave the covers alone: do not remove the connector cover when no expansion unit is fitted.
Function test before commissioning: operate each input in turn and confirm the contactors drop and the machine does not restart by itself. Then hold one contactor from releasing by hand and confirm the unit can no longer be reset.
06Failure modes and maintenance
Common problems, causes and actions
Symptom
Cause
Action
No response to reset
The feedback loop is open (a contactor stuck, or the auxiliary contact not wired), or only one channel has operated
Check the contactors; open and close both channels
Does not work at power-up
The supply rises too slowly
Let the supply settle before energising the unit
Output comes and goes
An input line shorted to earth or between channels, so the thermistor acts
Check the wiring; the unit recovers automatically once the fault is cleared
Reset fails after many operations
The forcibly guided relay has reached its life
Replace it on count
A contactor sticks and the machine keeps running
Only one contactor is used, or no feedback is wired
Use two contactors in series and wire the feedback loop
Compiled from the precautions in the Omron G9SA data sheet (page 16).
07Common design mistakes
Using an ordinary interface relay or a standard PLC output for the emergency stop circuit. Neither a welded contact nor a runaway program can be detected.
One contactor only, with no feedback. Once the contactor sticks, cutting the safety relay makes no difference.
Treating an auxiliary normally closed contact as a safety contact. Auxiliary contacts serve for monitoring only.
Automatic reset on an emergency stop or door switch, with no separate start button. Release the emergency stop and the machine starts by itself.
Stop category 0, cutting the supply, on a motor with large inertia. It then coasts for a long time. Where a controlled stop is needed, choose the delayed type with a delay longer than the slowing time.
Claiming PLe by copying a catalogue example. The level of a safety circuit is set by the risk assessment and must be verified by qualified persons to GB/T 16855.1 (ISO 13849-1) and related standards; the delayed output itself reaches only PLd / category 3.
Safety-related parts of control systems: design principles, PL and category; verification
IEC 62061
Functional safety of safety-related electrical control systems
EN 60947-5-1, GB 14048.5
Control circuit devices and switching elements (certification basis of the G9SA)
EN 50205
Relays with forcibly guided contacts (certification basis of the G7SA)
EN 574
Two-hand control devices (certification basis of the G9SA-TH301)
IEC 60204-1
Electrical equipment of machines, general requirements (stop categories and the like)
From the certification standards in the Omron G9SA data sheet (page 16), the Safety Relays product presentation and the Troax standards table. Edition years follow the current versions.
Tables and formulas are rearranged from the sources above. Verify against the current standard and the manufacturer catalogue before finalising a design. Updated 2026-11-17
ONLY ON MECHWIKI / SELECT · BUY · MAINTAIN
Buying and using: calculators, sellers, uses
The notes below cover the “Machine safety” category. MechWiki prepared these category notes from public standards and engineering references. Use the selected manufacturer’s catalog for ratings, life factors and dimensions.
07 / SELLERS
Who sells it
The directory links to manufacturer selection and CAD resources and identifies the maker of the pictured example. Check stock and lead time with the supplier. Price comparison and ranking are not available yet.
Representative series and official product pages; a manufacturer may offer other suitable series. Product ranges, availability and applicability are governed by manufacturer information. This is not a ranking, recommendation or equivalence judgment.
OMRONIndustrial automation control, sensing and safety products.
Emergency-stop, guard-door and safety-light-curtain circuits.
Machine frame with guard doorsSchematic, not to scaleArrow: Safety door switch
Area guarding for robot cells and automated linesSafeguarding loading and unloading openings on presses and press-fit stationsMachine service-door interlocksLine-wide emergency stops and zoned stops
Equipment breakdowns on this site that use this component family: