Image copyright belongs to the manufacturers or original authors. Brands and models identify illustrations; consult official documentation when selecting parts.
ENGINEERING GUIDE
Selection and design guide
A crimp terminal is a metal part crimped onto the end of a wire. In control cabinets the common types are ferrules (DIN 46228-1 without insulation, -4 with a plastic collar) and ring terminals (DIN 46234). The metal tube of a ferrule must match the strip length required by the terminal block. In the Schneider DZ5CE range, sizes from 0.5 to 2.5 mm² have an 8 mm tube and 14 mm overall length. The 4 mm² size has a 10 mm tube, and sizes from 6 to 16 mm² have a 12 mm tube. The plastic collar runs from Ø3.1 mm for 0.5 mm² to Ø9.6 mm for 16 mm². Colours follow either DIN or the French NF C 63-023 system, so do not identify a cross-section by colour alone. Select by wire cross-section, the clamping space of the terminal (the Siemens push-in type accepts at most 2.4 × 2.8 mm) and the matching crimping tool.
01Construction and how it works
A crimp terminal uses a crimping tool to compress and deform a metal tube or barrel together with the wire. This forms the connection between conductor and terminal at room temperature, with no solder. WAGO requires a method that produces a gas-tight crimp. Its Variocrimp 4 tool (206-1204) is one example. Only then is the contact durable and reliable.
Why flexible wire needs a ferrule: if fine-stranded flexible wire is screwed directly into a terminal, the strands spread out, are cut, or escape from the clamp. The screw terminals of the Siemens 3RP25 time relay state plainly that 'flexible wire without a ferrule is not allowed'. The Siemens 8WH6 push-in terminal accepts rigid wire and flexible wire with a ferrule directly. The 2.5 mm² terminal accepts wires from 0.34 mm². For flexible wire without a ferrule, press the button with a screwdriver to open the spring before inserting the wire.
Dimension definitions of a WAGO ferrule with a plastic collar. l1 is the overall length, l2 is the metal tube length, which is the part entering the terminal clamping point. d1 and s1 are the inner diameter and wall thickness of the metal tube. d2 and s2 are the inner diameter and wall thickness of the plastic collar. The wire enters from the plastic collar end on the right. All stripped conductor must be inside the metal tube before crimping.Source: WAGO product page, Ferrule 216-204, dimension drawing
Common crimp terminal types in control cabinets
Type
Basis
Where used
Key point
Ferrule (no plastic collar)
DIN 46228-1
Screw or push-in terminal blocks, relays, circuit breaker terminals
Small outer diameter, easier than the collared type in narrow terminals. WAGO notes that a plastic collar may further reduce the maximum connectable cross-section
Ferrule (with plastic collar)
DIN 46228-4
Same as above; most common in cabinets
The collar guides insertion and keeps strands covered. Colour indicates the cross-section
Twin ferrule
Maker's model
Two wires in one clamping point
The Siemens 8WH2 2.5 mm² terminal allows only 0.5 mm² twin ferrules. The 4 mm² terminal allows 0.5~1 mm²
Ring terminal (round lug)
DIN 46234
Bolt or stud connections: PE bars, motor terminals, transformers
Hole matches thread sizes M2.5~M16. It cannot slip off if the screw loosens slightly
Spade, pin, butt splice and others
Maker's model
Spade types can be removed without taking out the screw. Butt splices extend a wire
LAPP's lug catalogue lists butt, spade, pin and tubular forms among others
Compiled from the WAGO website's Ferrules practical tips, the Siemens ALPHA FIX Terminal Blocks catalogue (LV 52·2017), pages 2/4~2/5 and 4/7~4/8, the LAPP lug catalogue page and the KB lug data sheet.
02Types and designation systems
Colours of collared ferrules: WAGO (to DIN 46228-4) compared with Schneider (to NF C 63-023)
Cross-section mm²
WAGO model
WAGO colour
Schneider model
Schneider colour
0.5
216-201
White
DZ5CE005
White
0.75
216-202
Grey
DZ5CE007
Blue
1.0
216-203
Red
DZ5CE010
Red
1.5
216-204
Black
DZ5CE015
Black
2.5
216-206
Blue
DZ5CE025
Grey
4
216-207
Grey
DZ5CE042
Orange
6
216-208
Yellow
DZ5CE062
Green
10
216-209
Red
DZ5CE102
Brown
16
216-210
Blue
DZ5CE162
White
WAGO data are from the product pages for each model (216-201, 216-208 and 216-210 state conformity to part 4 of DIN 46228). Schneider data are from the DZ5CE product data sheets, where the standard column is NF C 63-023. The two colour systems differ at 0.75, 2.5, 4, 6, 10 and 16 mm². WAGO also has a 2.08 mm² (AWG 14) yellow 216-205. Use only one colour system in a cabinet. Write cross-section, not colour, on the drawings.
From the Schneider DZ5CE005~DZ5CE162 product data sheets, downloaded 2026-11-24. Material: copper (ISO 1337), with a halogen-free plastic collar. Operating temperature is -20~+105 °C. The data sheet does not say whether 'Tube diameter' is internal or external. It is taken here as external. When checking the clamping point, measure the actual part.
Selected LAPP KB ring terminals (DIN 46234, tinned copper)
Cross-section mm²
Thread
L mm
N mm
d mm
W mm
0.5~1.5
M3
11
6
1.6
6
0.5~1.5
M4
12
7
1.6
8
0.5~1.5
M5
13
8
1.6
10
1.5~2.5
M4
12
7
2.3
8
1.5~2.5
M5
14
9
2.3
10.1
4~6
M4
14
8
3.4
8
4~6
M10
21
15
3.6
18
10
M6
17
9
4.5
11
16
M8
29
12
5.8
14
25
M8
33
14
7.5
16
35
M10
36
15
9
18
From pages 1~3 of the LAPP Solderless cable lugs KB data sheet DB63204015EN. L is the distance from the end of the crimp barrel to the hole centre. N is from the start of the ring to the hole centre. d is the bore of the barrel and W is the ring width. Models marked with an asterisk are not to DIN 46234, according to the data sheet. These are 0.5~1.5 mm² with M6/M8/M10, 1.5~2.5 mm² with M10/M12 and 4~6 mm² with M5/M6/M8/M12. LAPP notes that these are traded products, not made by LAPP.
03Key parameters
Applicable cross-section: ferrules are marked with a single cross-section (0.5, 0.75, 1.0, 1.5, 2.5 ... mm²). Ring terminals are often marked with a range (LAPP KB: 0.5 to 1.5, 1.5 to 2.5 and 4 to 6 mm²). Above 10 mm² a single cross-section is used.
Metal tube length: this must match the strip length required by the terminal block (WAGO). In the Schneider DZ5CE range, 0.5 to 2.5 mm² all use 8 mm. The 4 mm² size uses 10 mm, and 6 to 16 mm² uses 12 mm.
Collar outer diameter: this decides whether a ferrule fits side by side in a narrow terminal and whether two can share one clamping point. Schneider gives Ø4.0 mm for 1.5 mm² and Ø4.7 mm for 2.5 mm².
Material and temperature: the Schneider DZ5CE has a copper tube and a halogen-free collar, rated -20 to +105 °C. The LAPP KB is tinned copper, rated -5 to +105 °C. The WAGO 216 series uses tinned electrolytic copper.
Conductor class: LAPP KB ring terminals suit copper conductors of classes 2, 5 and 6, that is stranded and fine-wire types.
Matching crimping tools: the LAPP KB uses the PEW 12 crimping tool. Sizes 0.5 to 10 mm² use die PEW 12.1071, and sizes 16 to 25 mm² use die PEW 12.033. WAGO recommends the Variocrimp 4.
Examples of equipment terminal requirements for ferrules
Device / terminal
Strip length
Flexible wire with ferrule
Note
Siemens 3RP25 time relay, screw terminals
10 mm
1 × 0.5~4 mm²; 2 × 0.5~1.5 mm²
Flexible wire without a ferrule is not allowed. 2 × 1.0 mm² collared ferrules may not fit. Use the uncollared type
Siemens 3RP25, push-in terminals
10 mm
1 × 0.5~2.5 mm²
The clamping space is rectangular. Maximum wire envelope is 2.4 × 2.8 mm
Catalogue lists only 1 × 4 / 2 × 2.5 mm² (solid or stranded)
Tighten to 0.8 N·m
Siemens 8WH2 spring terminal, 2.5 mm²
10 mm
0.25~2.5 mm² with or without a collar; twin ferrule 0.5 mm²
Gauge A3
From pages 38 and 41 of the Siemens 3RP25 manual, page 368 of the Siemens 3SU1 system manual, with reference to a similar table on page 372 written to DIN 46228. Also from page 8 of the Finder 80 series catalogue and page 4/8 of the Siemens ALPHA FIX catalogue.
04Dimensions, interfaces and installation space
A crimp terminal is small in itself. What really limits the layout is how it fits the clamping point of the terminal block: whether the cross-section is right, the tube length is right, the collars fit side by side, and how many wires share one point. The table below uses the Siemens ALPHA FIX 8WH terminal block as an example. It puts terminal width, allowed ferrule cross-section, strip length and the IEC 60947-1 plug gauge together. It then compares these with the collar outer diameter of a Schneider DZ5CE ferrule of the same cross-section.
Terminal specifications, clamping space and ferrule dimensions compared (Siemens 8WH terminal blocks + Schneider DZ5CE ferrules)
Terminal (Siemens)
Width mm
Flexible wire with ferrule mm²
Strip mm
Gauge
Collar outer diameter / tube length of same-size ferrule (Schneider)
8WH2 spring type 1.5 mm²
4.2
0.25~1.5; twin 0.5
10
A1
1.5 mm²: Ø4.0 / 8 mm
8WH2 spring type 2.5 mm²
5.2
0.25~2.5; twin 0.5
10
A3
2.5 mm²: Ø4.7 / 8 mm
8WH2 spring type 4 mm²
6.2
0.25~4; twin 0.5~1
10
A4
4 mm²: Ø5.4 / 10 mm
8WH6 push-in 2.5 mm²
5.2
0.14~2.5 (push-in 0.34~2.5)
10
—
2.5 mm²: Ø4.7 / 8 mm
8WH6 push-in 4 mm²
6.2
0.25~4 (push-in 0.5~4)
12
—
4 mm²: Ø5.4 / 10 mm
8WH6 push-in 6 mm²
8.2
with collar 0.5~6
12
A5
6 mm²: Ø6.9 / 12 mm
8WH6 push-in 10 mm²
8.2
with collar 0.5~10
18
A6
10 mm²: Ø8.4 / 12 mm
8WH6 push-in 16 mm²
12.2
with collar 0.5~16
18
A7
16 mm²: Ø9.6 / 12 mm
Terminal data are from pages 2/4~2/6 and 4/7~4/8 of the Siemens ALPHA FIX Terminal Blocks catalogue LV 52·2017. Ferrule dimensions are from the Schneider DZ5CE product data sheets. A gauge is the IEC 60947-1 plug gauge code. It shows the wire envelope the clamping mouth can accept. A higher number means a larger opening. '—' means the page does not list a value. The 8WH6 10 and 16 mm² terminals need an 18 mm strip. That is longer than the 12 mm tube of the same-size Schneider ferrule. Choose a ferrule to the length required by the terminal maker.
Collar diameter versus terminal width: the collar of a 2.5 mm² ferrule is Ø4.7 mm. In a 5.2 mm wide 2.5 mm² terminal this leaves about 0.5 mm. The same collar will not fit a 4.2 mm wide 1.5 mm² terminal position. On a small terminal, using a larger cross-section is not just a question of whether it can be clamped.
The clamping space of a push-in terminal is rectangular: the Siemens 3RP25 manual states that the push-in clamping mouth is rectangular. The wire, including the crimped ferrule, must not exceed 2.4 × 2.8 mm. The orientation of the mouth may require a rectangular ferrule to be inserted 'on edge'. A crimp that forms a rectangular profile is recommended. Trapezoidal crimping (Trapezcrimpung) is often suitable. When the wire fills the full height of the mouth, the spring is already fully open. Releasing the wire to remove it then becomes difficult.
Two wires: to put two wires in one clamping point, use a twin ferrule. Stay within the cross-section allowed by the terminal catalogue. The Siemens 8WH2 2.5 mm² terminal allows only 0.5 mm² twin ferrules. The 3RP25 notes that two 1.0 mm² collared ferrules may not fit together. An uncollared type can be used instead.
A plastic collar reduces the connectable cross-section: WAGO explains that a ferrule makes the wire thicker. The wire can no longer be connected at the terminal's stated maximum cross-section. With a collar, the collar may stop the wire going fully in. The maximum cross-section must be reduced further.
Space for ring terminals: check ring width W against the spacing of barriers between studs and the clearance to adjacent terminals. For example, the LAPP KB 4~6 mm² has an 18 mm ring width with an M10 thread, but only 8 mm with an M4. For the same cross-section, a smaller thread markedly reduces the space needed. It must still match the stud thread.
Duct and bend space: a ferrule is a rigid section 14 to 24 mm long. It cannot be bent within that length. Between the terminal block and the duct, allow the rigid length plus the bend radius. See the wiring duct entry.
Technical drawing and first part of the dimension table for LAPP KB ring terminals (DIN 46234). L is the distance from the end of the crimp barrel to the centre of the mounting hole. N is from the start of the ring to the hole centre. N1 is from the hole centre to the end of the ring. d is the bore of the barrel and W is the ring width. The table lists dimensions for 0.5~1.5 mm² and 1.5~2.5 mm² with M2.5~M10 threads, and the die PEW 12.1071 used. Models marked with an asterisk are not to DIN 46234.Source: LAPP, Solderless cable lugs KB data sheet DB63204015EN (2025-05-20 edition), page 1
1 Define the wireSpecify the cross-section in mm² or AWG, the conductor class (rigid, stranded or fine flexible), and the insulation outer diameter. Ferrules are mainly for fine flexible wire. Rigid wire is usually connected directly. Some equipment, such as the Siemens 3SU1, also gives an allowed cross-section for rigid wire with a terminal.
2 Check the equipment terminal requirementsIn the catalogue for the terminal block or device, find the allowed cross-section for flexible wire with a ferrule, the strip length, whether two wires are allowed, and whether a collar makes a difference. This step sets the upper limit for the ferrule size.
3 Choose the ferrule sizeMatch the cross-section to the wire. The metal tube length must match the strip length (WAGO). The collar must fit within the terminal width. For two wires, choose a twin ferrule.
4 Standardise the colour systemThe colours of DIN 46228-4 and NF C 63-023 differ. At 2.5 mm² one is blue and the other grey. Use ferrules from one supplier throughout the cabinet. Or write the cross-section to colour table in the work instructions.
5 Choose ring terminals by threadThe hole matches the stud thread, and the cross-section matches the crimp barrel. Then check that ring width W fits between the barriers. Prefer models to DIN 46234.
6 Choose the crimping toolUse the tool and die specified by the terminal maker. For the LAPP KB these are PEW 12 plus PEW 12.1071 or PEW 12.033. For push-in terminals, prefer a tool that produces a rectangular or trapezoidal crimp.
Examples of choosing ferrules for a terminal block
Wire
Terminal block
Check result
1.5 mm² fine flexible wire, single
Siemens 8WH2 2.5 mm² spring terminal (5.2 mm wide, 10 mm strip)
Cross-section within 0.25~2.5 mm². The 1.5 mm² ferrule collar is Ø4.0 mm, less than 5.2 mm. Choose the tube length for the 10 mm strip
Two 1.0 mm² wires in one clamping point
Siemens 8WH2 2.5 mm² spring terminal
Not allowed: this terminal permits only 0.5 mm² twin ferrules. Use a bridge or one more terminal
Two 1.0 mm² wires in one clamping point
Siemens 3RP25 screw terminal
Cross-section within 2 × 0.5~1.5 mm², but two collared ferrules may not fit. Use uncollared ferrules
2.5 mm² fine flexible wire
Siemens 3RP25 push-in terminal
Cross-section within 1 × 0.5~2.5 mm². After crimping, the envelope must not exceed 2.4 × 2.8 mm. Use a rectangular or trapezoidal crimp
Data from page 4/8 of the Siemens ALPHA FIX catalogue, pages 38 and 41 of the Siemens 3RP25 manual, and the Schneider DZ5CE015 data sheet.
1 Strip the wireStrip to the length required by the equipment, without damaging the strands. Straighten the strands. Do not twist them into a rope before cutting.
2 Fit the ferruleInsert all strands into the metal tube, with the insulation reaching into the plastic collar. If the conductor is too long it will show outside and fail the insulation requirement. If it is too short the contact is unreliable (WAGO).
3 CrimpCrimp fully with the specified tool and die to form a gas-tight joint. For push-in terminals, prefer a tool that forms a rectangular or trapezoidal section (Siemens 3RP25 manual).
4 Insert into the terminal blockContact is best when the crimped face is parallel to the contact face inside the terminal. Hold the wire short and insert it in one motion. Use a tool if needed. Do not leave a long length of wire above the ferrule to push with, or the wire may bend and be damaged above the terminal (WAGO).
5 CheckPull gently to confirm it is held. Tighten screw terminals to the torque specified by the equipment. For example, the Finder 80 series uses 0.8 N·m and the Siemens 3SU1 uses 0.8~0.9 N·m.
After crimping a ring terminal, fit heat-shrink tubing or an insulating sleeve. For bolted connections, fit washers and spring washers as the stud requires. Do not stack more ring terminals back to back than the stud allows.
In series production, carry out first-article and spot checks as required by the tool and terminal makers. Check appearance, dimensions after crimping and pull-out. Use the maker's data for the acceptance criteria.
Electrical design and wiring are done by qualified electricians to GB/T 5226.1 (IEC 60204-1) and similar standards.
07Failure modes and maintenance
Common problems, causes and actions
Symptom
Common cause
Action
Ferrule pulls out of the clamping point
Ferrule cross-section too large, leaving space inside the tube; wrong die; insufficient crimp
Select the ferrule by cross-section, use the specified die and check pull-out on the first article
Strands show outside the tube or collar
Strip too long; some strands did not enter the tube
Set strip length to the metal tube length; recrimp
Wire cannot go fully in; poor contact
Collar blocks the clamping mouth; tube shorter than the strip length
Use an uncollared ferrule or one with a tube matching the strip length
Wire cannot be removed from a push-in terminal
Crimped envelope fills the clamping mouth (maximum 2.4 × 2.8 mm for the Siemens 3RP25); the spring is fully open
Use a rectangular or trapezoidal crimp, or a smaller cross-section
Terminal heats up and discolours
Two wires forced into a point not approved for two; poor crimp; insufficient screw torque
Use a twin ferrule or add a terminal; recrimp; tighten to torque
Wrong cross-section connected by colour on site
DIN and NF colour systems mixed in one cabinet
Use one supplier; mark cross-section on drawings and wire numbers
Ring terminal will not fit or touches a barrier
Ring width W too large because the thread was oversized
Select the hole to the stud thread and check W
Compiled from the WAGO ferrule practical tips, the Siemens 3RP25 manual, the Siemens ALPHA FIX catalogue, and the Schneider DZ5CE and LAPP KB data sheets.
Maintenance: a crimp is a one-time operation. If it is damaged, cut it off and make a new one. Do not open a used ferrule and reuse it. On equipment with strong vibration, check screw terminals regularly for looseness. Where a catalogue such as the Schneider XB5 states that a terminal has a locking feature and needs no periodic retightening, follow the maker's instruction.
08Common design mistakes
Stocking parts by colour alone. At 2.5 mm², the DIN system is blue and Schneider (NF C 63-023) is grey. At 4 mm² one is grey and the other orange.
Tube length not matched to strip length. If the terminal block needs an 18 mm strip and the ferrule tube is 12 mm, the conductor either shows outside or is not held by the metal tube.
Choosing a ferrule at the terminal block's maximum cross-section. WAGO states clearly that a ferrule reduces the maximum connectable cross-section. A plastic collar reduces it further.
Forcing two wires into one clamping point. Use either a twin ferrule allowed by the terminal or a bridge. The Siemens 8WH2 2.5 mm² terminal allows only 0.5 mm² twin ferrules.
Using a round or hexagonal crimp for a push-in terminal, leaving too large an envelope. The clamping mouth of the Siemens 3RP25 is only 2.4 × 2.8 mm. A rectangular or trapezoidal crimp is recommended.
Choosing a ring terminal one thread size larger 'for easier fitting'. Ring width W then grows. It may touch a barrier, and the contact area after tightening is smaller.
Crimping with general-purpose pliers. Without the matching die, no gas-tight crimp is formed. The wire pulls out at once.
09Standards and manufacturer ranges
Standards cited in the material
Standard
Subject
Source
DIN 46228-1
Ferrules without a plastic collar
WAGO website ferrule notes
DIN 46228-4
Ferrules with a plastic collar, including colours
WAGO website ferrule notes and 216 series product pages
NF C 63-023
French ferrule standard, used by Schneider DZ5CE
Schneider DZ5CE product data sheets
DIN 46234
Solderless ring terminals
LAPP KB data sheet
ISO 1337
Copper material used in Schneider DZ5CE ferrule tubes
Schneider DZ5CE product data sheets
IEC 60947-7-1
Terminal blocks for copper conductors
Siemens ALPHA FIX catalogue
IEC 60947-1
Plug gauges (A1~A7, B5~B9 and others)
Siemens ALPHA FIX catalogue
Current editions apply.
WAGO: the 216 series ferrules, with and without a plastic collar, and the Variocrimp 4 crimping tool.
LAPP: KB series solderless ring terminals, which are traded products, and the PEW 12 crimping tool.
Phoenix Contact, Weidmüller and Klauke also offer complete ranges of ferrules, ring terminals and crimping tools. Use their own catalogues for specifications.
WAGO website, Ferrules practical tips (English) ↗DIN 46228-1/-4 tinned copper ferrules. Tube length must match strip length. A ferrule reduces the maximum connectable cross-section, and a collar reduces it further. Crimp face parallel, short grip and insert. Gas-tight crimp and the Variocrimp 4 (206-1204)
LAPP, Solderless cable lugs KB data sheet DB63204015EN, 2025-05-20 ↗Page 1: material, conductor classes, cross-sections 0.5~240 mm², threads M2.5~M16, temperature, DIN 46234, tool PEW 12 and technical drawing. Pages 1~3: dimension tables (L, N, N1, d, W and dies). Models with an asterisk are not to DIN 46234
Siemens, ALPHA FIX Terminal Blocks catalogue LV 52·2017 (English) ↗Pages 2/3~2/6: 8WH6 push-in terminal dimensions, ferrule cross-sections, push-in cross-sections, strip lengths and gauges A5~A7. Pages 4/7~4/8: 8WH2 spring terminal ferrule cross-sections with and without a collar, twin ferrule cross-sections, strip lengths and gauges A1/A3/A4. Chapter 3: gauge B5~B9 for 8WH1 screw terminals
Siemens, Zeitrelais 3RP25 Gerätehandbuch, 09/2019, A5E31947765001A (German) ↗Page 38: terminal connection data (flexible wire without a ferrule not allowed; space issue with 2 × 1.0 mm² collared types). Page 41: push-in terminal rectangular clamping space 2.4 × 2.8 mm, trapezoidal crimp, wire filling the full height hard to release
Tables and formulas are rearranged from the sources above. Verify against the current standard and the manufacturer catalogue before finalising a design. Updated 2026-11-24
ONLY ON MECHWIKI / SELECT · BUY · MAINTAIN
Buying and using: calculators, sellers, uses
The notes below cover the “Relays, wiring & enclosures” category. MechWiki prepared these category notes from public standards and engineering references. Use the selected manufacturer’s catalog for ratings, life factors and dimensions.
07 / SELLERS
Who sells it
The directory links to manufacturer selection and CAD resources and identifies the maker of the pictured example. Check stock and lead time with the supplier. Price comparison and ranking are not available yet.
Schneider ElectricElectrical, industrial control and energy-management products and support.
For bolted termination in distribution cabinets and motor terminal boxes. Check the conductor cross section and stud diameter when selecting.
Control cabinet (door and mounting panel)Schematic, not to scaleArrow: Relays & terminals
Isolation and amplification between PLC outputs and loadsTransition between cabinet and field cablingMounting and protection of machine electrical componentsField push-button and junction boxes