COMPONENT / THERMOCOUPLE

Thermocouple / RTD

Thermocouple / RTD · Hotset
Manufacturer illustration · HotsetPictured model: hotcontrol sheathed thermocouple / Pt100Original source
01 / INTRODUCTION

What is it?

A probe that measures temperature using the thermoelectric effect at the junction of two conductors.

02 / CONSTRUCTION

Construction & recognition

Two conductors meet at the measuring point. In the sheathed type the thermocouple wires and insulating powder are enclosed in a metal sheath.

03 / APPLICATIONS

Common applications

For temperature measurement on molds, heaters and measuring points that are hard to reach, and can be mounted to follow the surface contour.

Browse this category

Image copyright belongs to the manufacturers or original authors. Brands and models identify illustrations; consult official documentation when selecting parts.

ENGINEERING GUIDE

Selection and design guide

A thermocouple measures temperature difference from the thermoelectric voltage at the junction of two metals; a resistance thermometer (Pt100/Pt1000) measures temperature from the change of platinum resistance with temperature. Taking the Endress+Hauser iTHERM TM131 as an example: a Pt100 to IEC 60751 class A has a tolerance of ±(0.15 + 0.002·|t|) °C, and a type K thermocouple to IEC 60584 class 2 is ±2.5 °C from −40 to 333 °C; fitted in a Ø9×1.25 mm straight thermowell, t90 in water is about 59 to 62 s. To select, first decide the principle and accuracy class, then the wiring (2/3/4-wire), insertion depth and thermowell.

01Construction and how it works

Thermocouple (TC): two conductors of different materials are joined at one end (the measuring junction); when there is a temperature difference between the measuring junction and the other end (cold junction, reference junction), a very small voltage, the thermoelectric voltage, can be measured at the open ends. Its size depends on the material pair and the temperature difference between the ends, so a thermocouple essentially measures a temperature difference: to get the absolute temperature at the measuring junction, the cold junction temperature must be known or measured separately and compensated. Common material pairs and their voltage–temperature relations are defined in IEC 60584 and ASTM E230 (Endress+Hauser TM131 Technical Information, page 5).

Resistance thermometer (RTD): measures temperature from the change of platinum resistance with temperature. A Pt100 is 100 Ω at 0 °C with a temperature coefficient α = 0.003851 /°C (Endress+Hauser); JUMO's platinum chip data give α = 3.850×10⁻³ /°C (0 to 100 °C). A Pt1000 is 1000 Ω at 0 °C and follows the same IEC 60751 characteristic. An RTD is a passive element: the instrument passes a measuring current through it, reads the voltage, converts it to resistance and then to temperature.

Two constructions of platinum resistance elements
ConstructionHow it is madeFeatures
Wire-wound (WW)Fine high-purity platinum wire wound bifilar in a ceramic former, sealed with ceramic top and bottomGood stability and repeatability, usable to 600 °C; larger, sensitive to vibration (≤ 3g at the measuring tip)
Thin-film (TF)A platinum film about 1 µm thick vacuum-deposited onto a ceramic substrate, photolithographically structured, then covered with a passivation layerSmall and vibration resistant; at high temperature the characteristic drifts from the standard curve, so class A tolerance generally holds only to about 300 °C

Compiled from Endress+Hauser iTHERM ModuLine TM131 Technical Information TI01373T (07.25), pages 5 and 27.

  • Cold junction compensation: JUMO explains that thermoelectric voltage is defined for a 0 °C reference temperature; the extension cable must run all the way to the reference point (the instrument's cold junction compensation point), and must be of the same material as the thermocouple or have equivalent thermoelectric characteristics, or a new "thermocouple" forms at the joint.
  • Polarity and input impedance: thermocouples must be wired with correct polarity; JUMO requires the receiving instrument's input impedance to be at least 1000 times the thermocouple circuit resistance, or the display will be in error.
  • What a short in the line does: if thermocouple wires short partway along, the short becomes a new measuring junction and the instrument shows the temperature at the short instead of an alarm.
  • RTD self-heating: the measuring current heats the platinum element, adding an error whose size depends on the current and the thermal conductivity and flow of the medium. Endress+Hauser says self-heating error is negligible with its iTEMP transmitters (which use a very small measuring current).

02Types and specification system

Common thermocouple types
TypeMaterial (positive–negative)IEC 60584-3 colours (+ / −)Recommended maximum temperatureNotes
KNiCr-NiAl (Ni)Green / white1000 °C (3 mm wire); TM131 measuring range −40 to 1100 °CMost common, wide range
JFe-CuNiBlack / white700 °C (3 mm wire); TM131 measuring range −40 to 750 °CPositive leg is iron, magnetic
TCu-CuNiBrown / white350 °CLow temperature and humid conditions; Omega states it suits moisture and low temperatures
NNiCrSi-NiSiPink / white1200 °C (maximum temperature in JUMO's table)More stable than K at high temperature; a replacement for K

Colours and recommended temperatures from JUMO's thermocouple FAQ page (DIN EN 60584); −40 to 1100 / 750 °C for K and J from Endress+Hauser TM131 Technical Information, page 9. The two makers give different upper limits for type J (700 and 750 °C); the former is the long-term recommendation for 3 mm wire. ASTM E230 colours differ from IEC: J white (+) red (−), K yellow (+) red (−) (TM131 page 14); take care with equipment exported to North America.

Platinum RTD tolerance classes (IEC 60751)
ClassTolerance °CTM131 wire-wound Pt100 rangeTM131 thin-film Pt100 (standard) rangeJUMO platinum chip (PCA/EG) range
AA (F0.1, formerly 1/3 B)±(0.1 + 0.0017·|t|)−50 to +250 °C0 to +150 °C−50 to +200 °C
A (F0.15)±(0.15 + 0.002·|t|)−100 to +450 °C−30 to +250 °C−70 to +300 °C
B (F0.3)±(0.3 + 0.005·|t|)−200 to +600 °C−50 to +400 °C−70 to +500 °C
2B (F0.6)———−70 to +500 °C

Tolerance formulas and TM131 ranges from Endress+Hauser TI01373T, page 22; JUMO column from JUMO data sheet 906121 (V4.00, 2019-10), page 3, with Pt100, Pt500 and Pt1000 sharing the same classes. |t| is the absolute value of temperature. The same class has different valid temperature ranges on different constructions; when ordering, check the range the maker gives for that construction.

IEC 60751 platinum RTD tolerance bands: horizontal axis temperature −200 to 600 °C, vertical axis maximum deviation ±3 °C; class B is widest, about ±3.3 °C at 600 °C, class A ends at 450 °C and class AA at 250 °C (dashed lines are extensions beyond the range valid for that construction), with all three narrowest at 0 °C
IEC 60751 platinum RTD tolerance bands: horizontal axis temperature −200 to 600 °C, vertical axis maximum deviation ±3 °C; class B is widest, about ±3.3 °C at 600 °C, class A ends at 450 °C and class AA at 250 °C (dashed lines are extensions beyond the range valid for that construction), with all three narrowest at 0 °CImage source: Endress+Hauser, iTHERM ModuLine TM131 Technical Information TI01373T/09/EN/07.25-00, page 22
Thermocouple tolerance classes (IEC 60584, reference junction 0 °C)
TypeClass 1Class 2
J±1.5 °C (−40 to 375 °C); ±0.004·|t| (375 to 750 °C)±2.5 °C (−40 to 333 °C); ±0.0075·|t| (333 to 750 °C)
K, N±1.5 °C (−40 to 375 °C); ±0.004·|t| (375 to 1000 °C)±2.5 °C (−40 to 333 °C); ±0.0075·|t| (333 to 1200 °C)
T±0.5 °C (−40 to 125 °C); ±0.4% of reading (125 to 350 °C)±1 °C (−40 to 133 °C); ±0.75% of reading (133 to 350 °C)

J, K and N from Endress+Hauser TI01373T, page 23; type T from Omega, ANSI and IEC Color Codes for Thermocouples, page 3 (EN 60584-2 / JIS C 1602). Type T also has a class 3: ±1 °C (−67 to 40 °C), ±1.5% of reading (−200 to −67 °C). Endress+Hauser notes that base-metal thermocouple materials are generally only guaranteed to tolerance above −40 °C and do not meet class 3; for low temperatures, materials must be selected separately.

North American ASTM E230 tolerances (whichever is greater)
TypeStandard limitsSpecial limits
J2.2 °C or 0.75% (0 to 750 °C)1.1 °C or 0.4%
K2.2 °C or 0.75% (0 to 1250 °C); 2.2 °C or 2% (−200 to 0 °C)1.1 °C or 0.4% (0 to 1250 °C)
T1.0 °C or 0.75% (0 to 350 °C); 1.0 °C or 1.5% (−200 to 0 °C)0.5 °C or 0.4% (0 to 350 °C)

Omega, ANSI and IEC Color Codes for Thermocouples, page 2. Endress+Hauser gives 1260 °C as the upper limit of the standard class for type K (TI01373T page 23), 10 °C different from Omega.

03Key parameters

  • Measuring range: TM131 thin-film Pt100 basic −50 to 200 °C, standard −50 to 400 °C, StrongSens −50 to 500 °C, wire-wound Pt100 −200 to 600 °C; type K and N thermocouples −40 to 1100 °C, type J −40 to 750 °C.
  • Tolerance class: see the two tables in the previous section. Note that Pt100 tolerance widens with temperature, and thermocouple class 2 above 333 °C is 0.75% of reading.
  • Response time t50 / t90: the time for the reading to reach 50% / 90% after a temperature step, measured to IEC 60751 in water at 0.4 m/s with a 10 K step. It is set mainly by the thermowell, not the element itself.
  • Vibration resistance: TM131 at the measuring tip: wire-wound Pt100 ≤ 3g, thin-film standard ≤ 4g, StrongSens and Ø6 mm QuickSens 60g, thermocouples J/K/N ≤ 3g.
  • Insulation resistance: RTD terminals to housing > 100 MΩ (25 °C, ≥ 100 V DC); thermocouples to IEC 61515, at 500 V DC > 1 GΩ at 20 °C and > 5 MΩ at 500 °C.
  • Measuring current (RTD): JUMO platinum chips recommend 1.0 mA for Pt100 (maximum 7 mA) and 0.1 mA for Pt1000 (maximum 1 mA).
  • Long-term stability: JUMO platinum chip R0 drift is at most 0.05% per year.
Effect of thermowell diameter and tip shape on response time (water 0.4 m/s, 10 K step, no thermal paste, typical values in s)
Thermowell / tipThin-film Pt100 standard t50 / t90QuickSens t50 / t90Wire-wound Pt100 t50 / t90Type K thermocouple t50 / t90
9×1.25 mm straight tip21 / 5911 / 4623 / 6220 / 60
9×1.25 mm reduced tip8 / 202 / 78 / 207 / 20
9×1.25 mm tapered tip15 / 424 / 1714 / 4113 / 40
11×2 mm straight tip32 / 9715 / 7139 / 12028 / 86
11×2 mm reduced tip7 / 192 / 610 / 208 / 20

Endress+Hauser TI01373T, page 23. Changing the same element to a reduced-tip thermowell cuts t90 from about 1 min to about 20 s; the document also says its fast-response thermowell can cut t90 to about 1/4 of a conventional design.

Self-heating coefficient and response time of the JUMO platinum chip element itself (PCA/EG type)
ItemValue
Self-heating coefficient E (water, 0.2 m/s)0.02 K/mW
Self-heating coefficient E (air, 2 m/s)0.2 K/mW
Response time (water, 0.4 m/s)t0.5 = 0.1 s, t0.9 = 0.3 s
Response time (air, 1 m/s)t0.5 = 3 s, t0.9 = 8 to 9 s
Insulation resistance (room temperature)> 10 MΩ

JUMO data sheet 906121, pages 3~4. The bare chip responds in under 1 s in water, but tens of seconds once in a thermowell, which shows that the thermowell and installation dominate the response.

04Outline, interfaces and installation space

Taking the Endress+Hauser iTHERM ModuLine TM131 industrial thermometer as an example (with terminal head, replaceable insert, optionally with welded thermowell). It consists of the terminal head, removable extension neck E, thermowell extension T, process connection and immersion length U; the insert diameter is Ø3 or Ø6 mm. Standard versions weigh 1 to 10 kg, heavier than many expect, so support must be considered when mounting vertically on thin-walled pipe.

Several TM131 thermowell versions: A thermometer for fitting into an existing thermowell (E is the replaceable extension neck length); B with continuous thermowell, similar to DIN 43772 forms 2G/F, 3G/F (T is the thermowell extension); C thermowell with hexagonal extension, similar to DIN 43772 forms 5, 8; D thermowell without extension, similar to DIN 43772 form 2; U is the immersion length into the medium, measured from the process connection
Several TM131 thermowell versions: A thermometer for fitting into an existing thermowell (E is the replaceable extension neck length); B with continuous thermowell, similar to DIN 43772 forms 2G/F, 3G/F (T is the thermowell extension); C thermowell with hexagonal extension, similar to DIN 43772 forms 5, 8; D thermowell without extension, similar to DIN 43772 form 2; U is the immersion length into the medium, measured from the process connectionImage source: Endress+Hauser, iTHERM ModuLine TM131 Technical Information TI01373T/09/EN/07.25-00, page 8
TM131 threaded process connections (male thread)
ThreadThread length TLWidth across flats SWNotes
M14×1.512 mm22 mmParallel thread with DIN 7603 form A 1.5 mm copper washer
M20×1.514 mm27 mmAs above
G ½ (DIN / BSP)15 mm27 mmAs above
G 1 (DIN / BSP)18 mm41 mmAs above
NPT ½8 mm22 mmTaper thread, sealing on the thread
R ½—22 mmTaper thread

Endress+Hauser TI01373T, pages 42~43. The document gives a maximum static pressure of 400 bar for the thread itself (at 400 °C, calculated for full thread engagement); the actual pressure rating also depends on the thermowell and temperature.

  • Terminal head: internal dimensions to DIN EN 50446 form B (flat lid), thermometer connection thread M24×1.5 or ½ NPT. Aluminium TA30A weighs 330 g, cable entries G ½, NPT ½, M20×1.5, IP66/68, −50 to +150 °C without head transmitter; polyamide TA20B weighs 80 g, entry M20×1.5, IP65, −40 to +80 °C (TI01373T pages 51~52).
  • Temperature limit with head transmitter: with an iTEMP head transmitter fitted, the terminal head ambient temperature is limited to −40 to +85 °C, −30 to +85 °C with display. On hot pipes, use the extension neck E or thermowell extension T to lift the terminal head away from the heat.
  • Terminals: insert leads have terminal lugs (1.3 mm diameter), and the ceramic terminal block comes in 3-wire, 4-wire and 6-wire (dual Pt100) versions (TI01373T pages 10 and 14).
  • Thermowell sizes: 9×1.25, 11×2, 12×2.5, 14×2, 16×3.5 mm and others; materials 316L (recommended ≤ 650 °C long-term in air), 316Ti (≤ 700 °C), Alloy600 (≤ 1100 °C) and others (TI01373T pages 40~42).
  • Flow velocity limit: the longer the cantilever into the medium, the lower the allowed flow velocity; it also depends on thermowell diameter, medium, temperature and pressure. Endress+Hauser gives curves for water and superheated steam at 50 bar and recommends checking with the thermowell strength calculation (Sizing Thermowell) in Applicator.

05Selection steps and calculation

  1. Choose the principleBelow 600 °C where accuracy and stability matter, prefer a platinum RTD; above about 600 °C, or where vibration resistance, a very thin probe or very low cost is required, use a thermocouple. First check which input types the temperature controller or input module supports.
  2. Choose the type or elementThermocouples: generally choose K; T for low temperatures and humidity; match the existing type where it must agree with old equipment or instruments. RTDs: choose Pt1000 for long leads, 2-wire connection or instruments with small measuring current; transmitters and most controllers default to Pt100.
  3. Set the accuracy classCalculate the tolerance at working temperature from the tolerance formula and compare it with the process requirement; also check the class's valid temperature range on the chosen construction (for example thin-film Pt100 class A holds only to within about 300 °C).
  4. Choose the wiringA 2-wire Pt100 includes the lead resistance in the reading; for more than a few metres from cabinet to probe use 3-wire, and 4-wire for high accuracy or calibration. Run thermocouples to the instrument with extension cable of the matching type.
  5. Set immersion length and thermowellImmersion length at least half the pipe diameter, with the tip reaching or slightly past the pipe centre on small pipes; add a thermowell where there is pressure, flow, corrosion or a need to change the insert without stopping. Check thermowell strength for flow and pressure with the maker's tool.
  6. Check response timeFor closed-loop temperature control or alarms, compare the thermowell t90 with the control cycle; where speed is needed choose a reduced tip or fast-response thermowell and a thin probe.
  7. Choose the outputFor long distances, heavy interference or PLC analogue input cards, fit a head transmitter in the terminal head with 4~20 mA or IO-Link output.
ΔT_A = ±(0.15 + 0.002·|t|) °C
ΔT_A
permissible deviation, Pt100 class A
t
measured temperature, °C

Example: at t = 200 °C, class A is ±0.55 °C and class B ±(0.3 + 0.005×200) = ±1.3 °C. Compare type K class 2: ±2.5 °C at 200 °C, and ±0.0075×600 = ±4.5 °C at 600 °C; class 1 at 600 °C is ±2.4 °C. Formulas from TI01373T pages 22~23.

ΔT_lead ≈ R_lead / (R0 · α)
ΔT_lead
lead wire error with 2-wire connection, °C
R_lead
total round-trip resistance of the two leads, Ω
R0
resistance at 0 °C: 100 Ω for Pt100, 1000 Ω for Pt1000
α
0.00385 /°C

R0·α is the sensitivity: about 0.385 Ω/°C for Pt100 and about 3.85 Ω/°C for Pt1000. Example: with 1 Ω of round-trip lead resistance in 2-wire connection, a Pt100 reads about 2.6 °C high and a Pt1000 about 0.26 °C. 3-wire uses the third wire to cancel lead resistance (provided all wires have equal resistance), and 4-wire separates the current and voltage wires, so it is essentially unaffected by the leads. This is also why JUMO stresses that its chip nominal values apply only at the standard lead length L1: 0.2 mm nickel leads are about 2.4 mΩ per millimetre, so changing the lead length may mean the class is no longer met (data sheet 906121, pages 2~3).

Δt_self = I² · R · E
Δt_self
self-heating error, K
I
measuring current, A
R
element resistance, Ω
E
self-heating coefficient, K/mW

Formula from JUMO data sheet 906121, page 3. Example: a Pt100 at the recommended 1 mA dissipates P = 0.1 mW, giving about 0.02 K self-heating in air (E = 0.2 K/mW); if the instrument uses the maximum 7 mA, P ≈ 4.9 mW, about 1 K in air. A Pt1000 at 0.1 mA dissipates only 0.01 mW.

Thermocouples and RTDs most often connect to temperature controllers; with cartridge heaters the position of the measuring point decides control performance; into a PLC the signal usually goes through a transmitter as 4~20 mATemperature Controller →Cartridge Heater →Programmable Logic Controller →

06Installation, adjustment and use

Pipe installation examples: 1 and 2 thermometer inserted vertically with immersion length U reaching near the pipe centreline (ØD in 1 is the pipe diameter); 3 inserted at an elbow along the flow direction; 4 inserted into the pipe at an angle, the arrow showing flow direction
Pipe installation examples: 1 and 2 thermometer inserted vertically with immersion length U reaching near the pipe centreline (ØD in 1 is the pipe diameter); 3 inserted at an elbow along the flow direction; 4 inserted into the pipe at an angle, the arrow showing flow directionImage source: Endress+Hauser, iTHERM ModuLine TM131 Technical Information TI01373T/09/EN/07.25-00, page 26
  • Immersion depth: if inserted too shallow, heat conducts away through the process connection and vessel wall and the reading drifts towards ambient temperature. Endress+Hauser requires an immersion length in pipes of at least half the pipe diameter; where that is not possible, install at an angle or in an elbow.
  • Mounting orientation: the TM131 has no orientation restriction, but the process must be able to drain itself.
  • Minimum immersion for calibration: when calibrating at 251 to 550 °C the insert must be immersed at least 300 mm, at 551 to 600 °C at least 400 mm; with a head transmitter calibrated at −196 °C, at least 150 mm (TI01373T page 25). This also indicates that a probe inserted too short is hard to measure accurately at high temperature.
  • Grounded and insulated thermocouples: TM131 thermocouple inserts come grounded (thermocouple wire joined to the sheath) or ungrounded, chosen when ordering. With the grounded type the signal wire is connected to the sheath and pipe, and if the instrument input is not isolated a ground loop can form; when several devices share a ground and readings jump, first check whether grounded types are used.
  • Extension cable: match type and colour, do not reverse polarity; run it all the way from probe to instrument terminals without extending with ordinary copper wire in between.
  • Process connection sealing: parallel threads (G, M) seal with a copper washer, taper threads (NPT, R) on the thread; apply tightening torque to the wrench flats of the thermowell or process connection, not to the terminal head.

07Failure modes and maintenance

Common problems, causes and remedies
SymptomPossible causeRemedy
Thermocouple reading changes with cabinet temperatureCold junction compensation point not at the instrument terminals; extension cable changed to copper partwayRun extension cable to the instrument terminals; check the instrument's cold junction compensation setting
Thermocouple reading lower than actual and steadyShort in the line partway, the short becoming a new measuring junctionCheck line insulation and terminals
Pt100 reads a few degrees high2-wire lead resistance; high contact resistanceChange to 3-wire / 4-wire or to Pt1000; tighten terminals
Slow reading response, temperature overshootThermowell too thick, tip too heavy; insertion too shallowChange to a reduced tip or fast-response thermowell; increase insertion depth
Reading jumpsGround loop, interference from power cables; grounded thermocouple sharing ground with instrumentSeparate signal and power cables, ground the shield at one end; change to insulated type
Insert open circuitVibration above the element's limit (wire-wound Pt100 and thermocouples ≤ 3g)Use a vibration-resistant insert (such as the 60g class); stiffen the mounting
Long-term driftLong use at high temperature, element ageingCalibrate periodically; JUMO chip drift at most 0.05% per year

Causes and data compiled from Endress+Hauser TI01373T, JUMO FAQ and data sheet 906121.

For maintenance, designs with a replaceable insert allow the insert to be pulled out and replaced or sent for testing without removing the thermowell or stopping the process; Endress+Hauser explains that only the insert is calibrated, and the calibration certificate gives Callendar-van Dusen coefficients from at least three points, which can be written into the transmitter for sensor–transmitter matching to reduce conversion error.

08Common design mistakes

  • Specifying only "Pt100" without class and construction. Even at class A, a thin-film element is valid only to within about 300 °C; at high temperatures check the range the maker gives.
  • Running a 2-wire Pt100 over a dozen metres or more. Lead resistance becomes several degrees of error directly; use 3-wire, change to Pt1000, or fit a transmitter nearby.
  • Extending a thermocouple with ordinary cable. A new thermocouple forms at the joint and the reading drifts with cabinet temperature.
  • Setting insertion length by "whatever fits". At less than half the pipe diameter the reading tends towards pipe wall and ambient temperature; calculate immersion depth.
  • Ignoring thermowell response time. The bare element responds in under 1 s, but in an 11×2 mm straight thermowell t90 can reach 70~120 s, and a control loop tuned for 1 s will oscillate.
  • Placing the terminal head directly above the heat source. The head transmitter allows only −40 to +85 °C; use an extension neck to gain distance.
  • Wiring equipment for export to North America to IEC colours. ASTM colours differ (type K yellow + / red −), and wires are easily reversed on site.
  • Fitting a long thermowell straight into a high-velocity pipe. Cantilevered thermowells risk vibration fracture; check against flow velocity.
The protection rating of terminal head cable entries and M12 plugs must suit the installation environmentM12 Circular Connector →Cable Gland →

09Related standards and maker series

Standards cited in the sources
StandardSubject
IEC 60751Characteristics and tolerances of industrial platinum resistance thermometers (classes AA, A, B)
IEC 60584-1 / -2 / -3Thermocouple EMF and tolerances (classes 1, 2, 3), extension cables and colours
ASTM E230 / ANSI MC96.1North American thermocouple tables, standard and special limits, colours
IEC 61515Mineral-insulated sheathed thermocouples, including insulation resistance requirements
DIN 43772Thermowell forms (forms 2, 3, 5, 8 and others)
DIN EN 50446Terminal head forms (form B flat lid)
DIN 7603Copper washers for sealing parallel threads

Numbers from Endress+Hauser TI01373T, JUMO documents and Omega's colour code document; use the current edition.

  • Endress+Hauser: iTHERM ModuLine TM131 (industrial, with thermowell or for fitting into an existing one), TM111 (direct installation, no thermowell); inserts iTHERM QuickSens (fast response) and StrongSens (60g vibration resistant).
  • JUMO: platinum chip element data sheet 906121 (Pt100 / Pt500 / Pt1000, classes F0.1 to F0.6), plus screw-in and insertion thermocouple and RTD series.
  • Omega: thermocouples, extension cables and connectors; its colour code and IEC / ANSI tolerance comparison document is directly available.

—Sources

  • Endress+Hauser, iTHERM ModuLine TM131 Technical Information TI01373T/09/EN/07.25-00 ↗Page 5 measuring principle (Pt100, α, wire-wound/thin-film, thermocouple); pages 7~8 construction and thermowell forms, E/T/U definitions; page 9 measuring ranges; pages 10 and 14 wiring and thermocouple colours; page 22 IEC 60751 tolerance formulas, tolerance band chart and ranges for each construction; pages 23~24 IEC 60584 / ASTM E230 tolerances, self-heating, response time table; page 25 minimum calibration immersion length, insulation resistance; page 26 installation requirements; page 27 vibration resistance, process temperature, flow velocity; pages 40~43 thermowell sizes, material temperatures, threaded process connections; pages 51~52 inserts and terminal heads
  • JUMO data sheet 906121, Platinum-chip temperature sensors with connection wires, V4.00 (2019-10-25) ↗Page 2 platinum chip types, classes F0.1 to F0.6, lead resistance 2.4 mΩ/mm; page 3 temperature coefficient, valid ranges per class, recommended/maximum measuring current, long-term drift, self-heating formula, measuring point and lead length; page 4 self-heating coefficients and response times (JUMO's original data sheet hosted in the RS document library)
  • JUMO, Thermocouples – An overview FAQ ↗DIN EN 60584 type materials, colours, recommended maximum temperatures; extension cable, input impedance, polarity and short-circuit notes
  • Omega, ANSI and IEC Color Codes for Thermocouples, Wire and Connectors ↗Page 1 suitable environments and temperature ranges per type; page 2 ASTM E230 standard/special limits; page 3 IEC (EN 60584-2) class 1, 2, 3 tolerances (including type T)

Tables and formulas are rearranged from the sources above. Verify against the current standard and the manufacturer catalogue before finalising a design. Updated 2026-11-25

ONLY ON MECHWIKI / SELECT · BUY · MAINTAIN

Buying and using: calculators, sellers, uses

The notes below cover the “Process sensors & switches” category. MechWiki prepared these category notes from public standards and engineering references. Use the selected manufacturer’s catalog for ratings, life factors and dimensions.

07 / SELLERS

Who sells it

The directory links to manufacturer selection and CAD resources and identifies the maker of the pictured example. Check stock and lead time with the supplier. Price comparison and ranking are not available yet.

08 / WHERE IT IS USED

Typical uses & where it sits in machines

For temperature measurement on molds, heaters and measuring points that are hard to reach, and can be mounted to follow the surface contour.

CrownBaseGuide pillarsMoving platenGuide bushesLower die & partHydraulic cylinderPiston & rod sealsO-ringsHosesPower unit (motor + pump)Valve stackAccumulatorHere: Processsensors & switchesPressure sensor
Four-pillar hydraulic press with power unitSchematic, not to scaleArrow: Pressure sensor
Supply and clamping pressure confirmationHydraulic system pressure monitoringVacuum grip confirmationFill level, roll diameter and clear-object detection (ultrasonic)