01 / INTRODUCTION
What is it?
A clean-air supply unit that houses a fan, a HEPA or ULPA filter and controls in one casing, installed individually in a ceiling grid.
02 / CONSTRUCTION
Construction & recognition
The fan draws return air from above and pushes it down through the filter, with an air-straightening section and an outlet flange. Each unit has its own EC or AC fan and can be speed-controlled alone or grouped. Because every unit carries its own fan, no central ducting or pressurised plenum is needed, which reduces the risk of contamination through ceiling bypass.
03 / APPLICATIONS
Common applications
Cleanrooms and laminar-flow benches, biosafety and pharmaceutical areas, electronics and semiconductors, hospital operating theatres.
Image copyright belongs to the manufacturers or original authors. Brands and models identify illustrations; consult official documentation when selecting parts.
ENGINEERING GUIDE
Selection and design guide
A clean air supply unit that packs an EC backward curved centrifugal fan, a HEPA/ULPA filter and control interfaces into one housing. It hangs from the ceiling grid on its module. For purchase, state the module size, filter grade and sealing method, the service side, either top or room side, the voltage, the air volume and the control method.
01Construction and operating principle
A fan filter unit, FFU, is a complete package. The upper housing holds a backward curved centrifugal fan with an EC motor. It draws return air from the plenum above the ceiling, or from a duct. It pressurizes the air and sends it down through the HEPA or ULPA filter below. Each unit has its own fan. You can set its speed on its own. Dozens or hundreds of units can also be controlled as a group over a network. When designing custom equipment such as a laminar flow hood, a clean bench or overhead supply for a machine, buy it as a filter with a built in fan. You do not need to design the fan yourself.
Components of the AAF Flanders AstroFan EC FFU (maker series example)
Part
Construction
Points to note
Housing
Aluminum or 304 stainless steel. Lifting tabs or mounting pads at the four corners, with handles
Optional white powder coat and 2 in aluminum foil insulation
Fan
Backward curved centrifugal impeller with an EC brushless DC motor, single phase 50/60 Hz
The catalogue claims 30%~40% energy saving over an AC motor
Air inlet
The fan inlet has a guard mesh. Round or rectangular inlet connections are optional
It can connect to a duct or draw from an open plenum
Pre filtration
An optional rectangular connection also serves as a pre filter frame. It takes particle or molecular contamination, AMC, media
Order the pre filter separately
Main filter
MEGAcel II eFRM membrane media for H13 and H14, or ePTFE for U15~U17. Glass fiber is also available
Order the filter separately from the housing. Include the filter code in the model number so the maker can check compatibility
Sealing
Gel seal with two component silicone gel, or a polyurethane foam gasket, 1/4 in thick × 3/4 in wide
The gel type uses a knife edge inserted into the gel
Control
MODBUS RTU platform, with an optional BACnet gateway
Group control by handheld or wall mounted controller
Compiled from pages 1, 2, 5 and 6 of AAF Flanders, AstroFan EC FFU, AFP-CS-113H.
Three ways of connecting an FFU to the ceiling grid, in section. Left, Top Side, top access: the AstroFan Housing sits on the TSS Filter Frame. The frame presses on the Grid / T-Bar Ceiling through a Gasket. A Gasketed Channel is a sealed channel, and Filter Media is the filter medium. Center, Roomside Change Grid, room side filter change, grid type: the RSR Adaptor Frame mounts on the grid. The RSR Filter is inserted from below and sealed with Gel, silicone gel. Right, Roomside Change Frame, room side filter change, frame type: the filter is held by Stud, Filter Retainer and Acorn Nut. A Grille sits below.Image: AAF Flanders, AstroFan EC FFU Fan Filter Unit, AFP-CS-113H
Chinese made FFUs often put operating status on the outside of the housing. A safety air guide cover sits over the top fan inlet. Handles on both sides help with lifting. The side carries an external / communication port for the group control cable. It also carries a fault indicator light and a current display. Inside is the group control board. With dozens or hundreds of units on the network, the central panel shows which unit has stopped and which is overloaded.
Example of the external features of a Chinese made FFU. The safety air guide cover is at the center of the top over the fan inlet. Stainless steel handles are at both ends. The side has an external / communication port. It also has a three color fault indicator light. The maker states that orange means a communication fault, green a motor fault and red an overload. A real time current display sits next to it. An intelligent group control board is inside.Image: Guangzhou Zijing Purification Equipment Co., Ltd., Calculation Method for FFU Quantity in Class 100, Class 1000 and Class 10000 Cleanrooms
For fan curves, system resistance and the fan laws, see the industrial fan article.Industrial fan / blower →
02Types and specification system
FFU sizes follow the ceiling grid module. US sizes are 2×2, 2×3, 2×4, 3×4 and 4×4 in feet. Metric equivalents include 600×600, 600×1210 and 1210×1210. Custom sizes are also possible. By service side there are two types. Top side access, TSS, means changing the filter from above the ceiling. Its construction is simple. Room side replaceable, RSR, means changing the filter from below inside the cleanroom. It has an aerosol injection port and a static pressure test port. This makes on site leak testing and validation easy. It is common in pharmaceutical and biological work.
Domestic ceilings are laid out on the grid centerline spacing, the module size. Common FFU modules are 1200×600 (4′×2′), 1200×900 (4′×3′) and 1200×1200 (4′×4′). The actual size of an FFU is somewhat smaller than the module. It must sit inside the grid cell. Calculate the filter size with the equation below. The fan housing is about 4 mm larger than the filter. With the common 55 mm wide grid, modules of 1200, 900 and 600 give filters of 1170, 870 and 570 mm. The housings are 1175, 875 and 575 mm.
d_actual = d_module − (b − 25)
d_actual
Actual size of the filter, mm; subscript actual for actual size. The fan housing is about 4 mm larger
d_module
Module size, the grid centerline spacing, mm; subscript module for module
b
Grid cross section width, mm; commonly 55 mm
Guangzhou Zijing Purification Equipment Co., Ltd., Calculation Method for FFU Quantity in Class 100, Class 1000 and Class 10000 Cleanrooms. The filter size follows this equation. The fan housing is about 4 mm larger.
An FFU mounted on a T-BAR ceiling grid. The grid is laid out in 1200 × 1200 cells, with 600 cells in the short direction. Cross, L and T connectors join the bars. Suspension rods hang from the slab, and leveling adjusters level the grid. FFUs, lights and blank panels all sit in the grid cells. At lower left is the T-BAR section, 55 mm wide and 60 mm high.Image: Guangzhou Zijing Purification Equipment Co., Ltd., Calculation Method for FFU Quantity in Class 100, Class 1000 and Class 10000 Cleanrooms
AstroFan EC FFU standard sizes (AAF Flanders series example)
Nominal size
1-1/2 in T-bar, mm
2 in T-bar, mm
Fan configuration
Maximum air volume, without filter
2×2
600×600
587×587
EC3
1200 CFM (2040 m³/h)
2×4
600×1210
587×1197
EC4
2000 CFM (about 3400 m³/h)
4×4
1210×1210
1197×1197
EC4
2000 CFM (about 3400 m³/h)
Taken from pages 1 and 5 of AFP-CS-113H. On page 1, the size column gives the maximum air volume for 2×4~4×4 as 2000 CFM / 2400 CMH. On page 5, the model description gives 2000 CFM / 3400 CMH. Using 1 CFM ≈ 1.699 m³/h, the correct value is about 3400 m³/h. The 2400 on page 1 is likely a printing error. Confirm with the maker before ordering. Custom sizes: EC3 is 580~720 mm wide and 580~1070 mm long. EC4 is 580~1220 mm wide and 915~1220 mm long, on page 5. The drawing on page 4 says 560~1220 mm for both width and length. The two do not agree.
Filter options (AAF MEGAcel II, maker series example)
Code
Grade / efficiency
Media
Common applications
H13E
H13, 99.99% at 0.3 µm
eFRM double layer expanded fluoropolymer membrane
Life sciences. Can be tested by photometer with oily aerosol, PAO
H14E
H14, 99.995% at MPPS
eFRM
Same as above
U15E
U15, 99.9995% at MPPS
ePTFE single layer expanded PTFE membrane
Microelectronics and equipment plants. Test with a particle counter, DPC
U16, U17
99.99995% and 99.999995% at MPPS
ePTFE
Same as above
H13G, H14G, U15G
Glass fiber filter of the same grade
Glass fiber
On request
Taken from pages 2 and 5 of AFP-CS-113H. MPPS is the most penetrating particle size. The catalogue says membrane media can be up to 100 times as strong as glass fiber. Glass fiber filters are available on request.
03Outline, connections and installation space
FFU layout requires three decisions. First, the ceiling opening size, or module. Second, the height to leave above the ceiling. Third, which side the service is done from. The AAF Flanders AstroFan EC FFU is used here as an example. It is one of the leading brands in clean filtration. For FFUs of the same 600×1200 class, different makers vary in housing height, lifting tab position and junction box position. When changing brand, check against the other maker's catalogue.
AstroFan EC FFU outline drawing, top access type. Top View: W is width and L is length. The round shape in the middle is the fan inlet with a guard mesh. The small box at lower right is the electrical parts, subject to the catalogue. Side View: the housing is 13.75 in high, 349.3 mm. The Mounting Pads / Hanging Tabs at the four corners, four in total, stand 1.88 in, 47.6 mm, above the housing. D is the total height including the filter frame. FD is the depth of the filter frame, TSS, or of the room side adaptor frame, RSR. The housing sits inside the frame. In the table below, Frame Style TSS has FD = 3.73 in, 94.9 mm, and D = 16.75 in, 425.5 mm. RSR has FD = 4.73 in, 120.2 mm, and D = 17.75 in, 451.0 mm. Dimensions not marked on the drawing are in inches.Image: AAF Flanders, AstroFan EC FFU Fan Filter Unit, AFP-CS-113H (Checkbox Submittal, drawing 600-00018 Rev D)
AstroFan EC FFU outline, mass and performance (AAF Flanders series example)
Size
Housing L×W×H, mm (plus lifting tabs)
Mass, kg
Voltage, V
Filter
Power, W
Noise, dB(A)
600×600
600×600×349 (+40)
11
115
Glass fiber 2 in H14 / eFRM 2 in H14 / ePTFE 1.5 in U15
91 / 72 / 82
50 / 48 / 50
600×600
Same as above
11
277
Same as above
72 / 70 / 76
50 / 47 / 50
600×1210
600×1210×349 (+40)
26
115
Same as above
152 / 113 / 124
56 / 54 / 56
600×1210
Same as above
26
277
Same as above
144 / 106 / 119
55 / 52 / 54
1210×1210
1210×1210×349 (+40)
32
115
Same as above
269 / 230 / 244
59 / 61 / 60
1210×1210
Same as above
32
277
Same as above
160 / 217 / 230
58 / 57 / 57
Taken from Performance Information on page 3 of AFP-CS-113H. Noise was measured at 90 FPM face velocity, about 0.46 m/s, and 0.36 in wg external static pressure, about 90 Pa. The measurement point was 1.5 m directly below the outlet. Tolerance is ±1 dB(A). Housing dimensions exclude the filter. For 1210×1210 at 277 V with a glass fiber filter, the 160 W power is clearly below the 217 W of eFRM at the same size. This reverses the pattern of the other rows. It is likely a printing error. Confirm with the maker before ordering.
Ceiling module versus actual FFU outline
Module
Grid
Actual FFU width × length
Source
2′ × 2′
1-1/2 in T-bar
23-5/8 × 23-5/8 in (600 × 600 mm)
AAF AstroFan EC
2′ × 2′
2 in T-bar
23-1/8 × 23-1/8 in (587 × 587 mm)
AAF AstroFan EC
2′ × 4′
1-1/2 in / 2 in T-bar
23-5/8 × 47-5/8 in (600 × 1210) / 23-1/8 × 47-1/8 in (587 × 1197)
AAF AstroFan EC
4′ × 4′
1-1/2 in / 2 in T-bar
47-5/8 × 47-5/8 in (1210 × 1210) / 47-1/8 × 47-1/8 in (1197 × 1197)
AAF AstroFan EC
600 × 600
55 mm wide T-BAR
Filter 570 × 570, housing about 575 × 575 mm
Zijing, from d_actual = d_module − (b − 25)
1200 × 600
55 mm wide T-BAR
Filter 1170 × 570, housing about 1175 × 575 mm
Zijing
1200 × 1200
55 mm wide T-BAR
Filter 1170 × 1170, housing about 1175 × 1175 mm
Zijing
AAF data comes from pages 3 and 5 of AFP-CS-113H. It states that unit dimensions follow the interface between the TSS or RSR filter frame and the grid. Zijing data comes from its FFU quantity calculation. A US 2′ module unit is nominally 600 mm. It cannot be swapped with a 575 mm housing on a metric 600 module. The first follows an imperial grid, the second a 55 mm domestic grid. State the grid system and grid width when ordering.
Grid and sealing type: on a standard T-bar grid, the filter frame presses onto the grid flange with a polyurethane gasket. It is a 1/4 in thick × 3/4 in wide dovetail gasket. A gel grid has silicone gel in its channel. The knife edge of the filter frame inserts into the gel to seal. AAF filter frames are designed for either a gasket or a gel. The gel must accept the knife edge without being cut through, according to AFP-CS-113H pages 2 and 6. The room side filter change, grid type, in the AAF section view uses gel sealing.
Height above the ceiling: the housing is 349 mm plus 40~48 mm for the lifting tabs. With the filter frame, total height D is 425.5 mm for TSS or 451 mm for RSR. Space above the fan inlet must also be left for air entry. An open plenum and a duct connection differ. Follow the catalogue.
Suspension: lifting tabs or mounting pads at the four corners. The ceiling grid carries the load, or separate hangers are used. Design this with the ceiling system.
Power supply: single phase 100~130 V or 200~277 V, 50/60 Hz, ordering code 1 / 2. Size circuits from the number of FFUs and the power of each unit. See the table above for unit power.
Control: MODBUS RTU bus with an optional BACnet gateway. One AstroDrive 100 handheld controller handles up to 100 units on one line, using ebmBUS or MODBUS. An AstroDrive 200 wall mounted controller handles up to 200 EC fans. It is IP65 and has digital inputs and outputs and dry contacts, on page 6.
Service side: TSS requires access from above the ceiling. RSR changes the filter and does aerosol leak testing from the room side. No access path above the ceiling is then needed.
Operating temperature: 25~115 °F, about −4~46 °C.
Catalogues and submittal drawings (maker websites)
AAF requires the customer to sign off the submittal drawing before production starts. CAD models are as provided by the maker.
04Key parameters
Parameters to state when ordering
Parameter
Description
Points to note
Module size
600×600, 600×1210, 1210×1210, or custom width × length
Openings differ between 1-1/2 in and 2 in wide grids
Service method
TSS top access / RSR room side replaceable
RSR has an aerosol injection port. TSS needs a filter with a central test port for testing
Filter grade and media
H13, H14, U15~U17; membrane or glass fiber media
Test methods differ. Use a photometer for eFRM membrane media and a particle counter for ePTFE
Sealing method
Gel or gasket
Loading: top load, top load with test port, or bottom load, with aluminum, stainless steel or painted grille
Face velocity / air volume
Operating point
Initial filter resistance rises with face velocity. Fan static pressure reserve must be enough
External static pressure
Resistance of inlet duct and pre filter
Catalogue noise is measured at 0.36 in wg, about 90 Pa
Voltage
100~130 V or 200~277 V
At the same size, the 277 V version generally uses slightly less power
Housing material and options
Aluminum / 304 stainless steel; coating, insulation, inlet connection and pre filter frame
Insulation is used for noise reduction or to prevent condensation
Control
MODBUS RTU, BACnet gateway, handheld or wall mounted group control
Agree the interface with the plant BMS in advance
Compiled from pages 1~6 of AFP-CS-113H.
Maximum initial filter resistance (MEGAcel II specification, maker series example)
Media
Nominal depth
Efficiency
Maximum initial resistance
eFRM
2.0 in
99.99% at 0.3 µm
0.25 in wg (about 62 Pa)
eFRM
2.0 in
99.995% at 0.12 µm
0.30 in wg (about 75 Pa)
ePTFE
2.0 in
99.9995% at 0.12 µm
0.26 in wg (about 65 Pa)
ePTFE
1.5 in
99.9995% at 0.12 µm
0.44 in wg (about 110 Pa)
Taken from the specification table on page 6 of AFP-CS-113H. The table does not state the corresponding face velocity. Page 3 has a resistance versus face velocity curve for 25~125 FPM. Read the curve at the selected velocity.
05Selection steps and calculation
Set cleanliness requirement and air supplySet the cleanliness class and airflow pattern from the process. ISO 5, Class 100, uses unidirectional flow. FFUs must cover the ceiling or the clean booth roof. ISO 6 to 9 generally use non unidirectional flow. Set air supply from the air change rate. In GB 50073-2013, ISO 5 unidirectional flow has a face velocity of 0.2 to 0.5 m/s. ISO 6 is 50 to 60 changes per hour. ISO 7 is 15 to 25 changes per hour. ISO 8 and 9 are 10 to 15 changes per hour. FFU maker experience values are generally higher. See the table below.
Set the module and unit countChoose 600×600, 600×1210 or 1210×1210 from the ceiling grid module. Domestic practice often uses 1200×600, 1200×900 and 1200×1200. Round up the unit count N = V·α / S. For Class 100, lay units across the whole ceiling. After layout, check that each unit's air volume does not exceed the catalogue maximum, the value without a filter.
Set the filterSelect by grade and test method. Life sciences often use H13/H14 eFRM with PAO photometer testing. Microelectronics often use U15 and above ePTFE with particle counter testing.
Check fan static pressure reserveExternal static pressure equals the resistance of the inlet duct or pre filter. The fan must deliver the required air volume against filter resistance plus external static pressure. Read the maker's curve. Leave margin at the operating point for resistance rise as the filter loads with dust.
Set service method and controlChoose RSR when room side leak testing and validation are needed. With many units, use bus group control. Agree the interface with the BMS.
Check electrical supply and noiseSize the electrical supply from the unit count and power per unit. Compare noise with site requirements using the catalogue test conditions, 90 FPM and 1.5 m below the outlet. Overall noise rises when many units run together. The maker's calculation governs.
Rated air volume of one FFU, m³/h. Catalogues commonly give 750 ~ 1200 or 750 ~ 1500 m³/h adjustable
Guangzhou Zijing Purification Equipment Co., Ltd., Calculation Method for FFU Quantity in Class 100, Class 1000 and Class 10000 Cleanrooms. Take S from the catalogue air volume at the actual external static pressure. Do not use the maximum air volume at zero static pressure.
Air change rate values
Cleanliness class
GB 50073-2013
FFU maker experience values (Zijing)
ISO 5 (Class 100)
Unidirectional flow, face velocity 0.2 ~ 0.5 m/s
FFUs cover the whole ceiling. Equivalent air change rate ≥ 200, typically taken as 230 changes per hour
ISO 6 (Class 1000)
50 ~ 60 changes per hour
50 ~ 100 changes per hour, typically 70 changes per hour
ISO 7 (Class 10000)
15 ~ 25 changes per hour
25 ~ 30 changes per hour
ISO 8 (Class 100000)
10 ~ 15 changes per hour
15 ~ 20 changes per hour
ISO 9 (Class 1000000)
10 ~ 15 changes per hour
12 ~ 15 changes per hour
The original Zijing text writes all classes as ISO5. Here they are arranged as Class 100, Class 1000, Class 10000, Class 100000 and Class 1000000, corresponding to ISO 5 ~ 9. Maker values are higher than the national standard. This leaves margin for people moving and doors opening. Unit counts and energy use rise as a result. Some industry sources use 75, 45 and 25 changes per hour for Class 1000, Class 10000 and Class 100000.
Sealing face: the channel of a gel sealed filter frame is filled at the factory with two component silicone gel. Do not cut through the gel layer when fitting it onto the knife edge. The gasket type uses a 1/4 in × 3/4 in dovetail polyurethane foam pad, AFP-CS-113H page 6.
Filter orientation and test port: if a top access unit needs leak testing or resistance measurement, the filter must have a center panel test port. The room side replaceable type comes with an aerosol injection port and a static pressure test port.
Factory testing: every FFU is fully tested and given a serial number. Test records can be traced. Every filter is scan tested for leaks to IEST-RP-CC034 or EN 1822. The label gives size, batch, serial number, measured efficiency and resistance.
Clean packaging: filters are made in an ISO 7 cleanroom and packed in an ISO 6 cleanroom. Double plastic bag packing is optional. Do not unpack before installation.
Commissioning: after networking, set the speed of each unit. Use face velocity measurements to confirm that all units deliver the same air volume.
07Failure modes and maintenance
Common problems, causes and actions
Symptom
Cause
Action
Air volume gradually falls
Filter resistance rises with dust; pre filter blocked
Replace the pre filter first. Raise speed to compensate. Replace the main filter when resistance exceeds the limit
Leak test fails
Damaged media or a leaking seal
Membrane media resists damage well. For gel sealing, check whether the gel has been cut through
An individual unit does not run or raises an alarm
Power supply, bus address or motor protection
Check bus communication and the unit alarm
Noise too high
Speed too high or external static pressure too high
Reduce inlet side resistance. Add insulation. Check the operating point
Condensation or contamination above the ceiling
Insufficient insulation or bypass leakage
Choose an insulated housing. Check the seal between housing and frame
Summarized from the construction and specifications in AFP-CS-113H. The source has no separate fault table.
08Common design mistakes
Treating 600×1200 as a universal size. A 1-1/2 in grid gives 600×1210. A 2 in grid gives 587×1197. Set the opening from the grid system.
Allowing only the housing height above the ceiling. You must also add lifting tabs, the filter frame and air inlet space. Total height of the RSR type reaches 451 mm.
Sizing by the air volume without a filter. The catalogue maximum is marked as excluding the filter. With a filter fitted, read the delivered air volume from the curve.
Mismatch between filter grade and test method. Choosing ePTFE when PAO photometer leak testing is required causes problems. So does choosing glass fiber when particle counting is required. Validation will fail.
Not checking compatibility when ordering the filter separately. AAF recommends including the filter code in the model number. The maker can then check that frame, filter and sealing method match.
Assuming the TSS type can also be changed from the room. Top access types require a person above the ceiling. The filter cannot be changed inside the cleanroom.
Adjusting each unit by hand when there are many. Design the group control interface from the start.
09Related standards and maker ranges
Standards appearing in the sources
Standard number
Content
Source
IEST RP-CC-036.1-2014
Recommended practice for FFU testing
AFP-CS-113H, page 3, note 1
JG/T 388—2012
Fan filter units
Same as above
GB/T 1236—2000
Industrial fans; performance testing using standardized ducts
Same as above
GB 9068—1988
Determination of sound power levels of heating, ventilation and air conditioning equipment
Same as above
IEST-RP-CC034, EN 1822
Scan leak testing of HEPA and ULPA filters
AFP-CS-113H, page 6
UL 900
Flammability classification of air filters
Same as above
Write version numbers as they appear in the sources. The current version governs.
AAF Flanders: AstroFan EC FFU with AFUA aluminum housing or AFUS stainless steel housing, and EC3 or EC4 fan stages. MEGAcel II eFRM / ePTFE filters and AstroDrive 100 / 200 controllers.
Camfil: fan filter unit product line, including the Pharmaseal series.
—Sources
AAF Flanders, AstroFan EC FFU Fan Filter Unit, AFP-CS-113H (10/22) ↗Page 1: product overview and sizes. Page 2: installation connection sections, TSS and RSR, and MEGAcel II media. Page 3: performance table, size, mass, power and noise, with test standard notes. Page 4: outline submittal drawing, drawing 600-00018 Rev D. Page 5: model coding and standard sizes. Page 6: technical specifications, filter specifications and AstroDrive controllers.
Tables and formulas are rearranged from the sources above. Verify against the current standard and the manufacturer catalogue before finalising a design. Updated 2026-11-25
TOOLS / CALCULATE
Related selection calculators
Use these calculators for a preliminary estimate, then verify the result against this entry, the manufacturer catalogue and installation limits. Results do not replace a specific model rating.
Combines a fan and high-efficiency filter in one unit to supply filtered air to a cleanroom or local controlled area.
Operating principle
The fan draws in air and overcomes resistance from the filter and air passages. Air passes through the high-efficiency filter and enters the protected area. Air velocity, filter seals and surrounding return air all affect cleanliness. Dust accumulation changes filter resistance and airflow.
Process sequence
Check installation and sealing
Start the fan and adjust supply airflow
Measure air velocity and its uniformity
Check filter integrity and room airflow patterns
Monitor operation
Service according to condition
Key inputs
Target environment and air supply layout
Filter type, pressure drop and fan operating point
Sealing, return air, particle generation and service clearance
Common issues
Clogged filters reduce airflow.
Seal bypass or filter damage can allow leakage.
Obstacles and other air supplies can disrupt local flow.
Scope and limitations
A fan filter unit supplies filtered air as part of the larger air conditioning system.
A room's cleanliness depends on the entire installation, including airflow and particle sources. Particle filters remove particles; gas purification requires separate treatment.
Functional modules
Fan motor
Provides the required airflow and pressure difference.
Prefilter
Captures larger particles and protects the downstream filter.