FFU cleanroom unit schematic
MechWiki · operating principle, not to scale

Purpose

Combines a fan and high-efficiency filter in one unit to supply filtered air to a cleanroom or local controlled area.

Operating principle

The fan draws in air and overcomes resistance from the filter and air passages. Air passes through the high-efficiency filter and enters the protected area. Air velocity, filter seals and surrounding return air all affect cleanliness. Dust accumulation changes filter resistance and airflow.

Process sequence

  • Check installation and sealing
  • Start the fan and adjust supply airflow
  • Measure air velocity and its uniformity
  • Check filter integrity and room airflow patterns
  • Monitor operation
  • Service according to condition

Key inputs

  • Target environment and air supply layout
  • Filter type, pressure drop and fan operating point
  • Sealing, return air, particle generation and service clearance

Common issues

  • Clogged filters reduce airflow.
  • Seal bypass or filter damage can allow leakage.
  • Obstacles and other air supplies can disrupt local flow.

Scope and limitations

  • A fan filter unit supplies filtered air as part of the larger air conditioning system.
  • A room's cleanliness depends on the entire installation, including airflow and particle sources. Particle filters remove particles; gas purification requires separate treatment.

Functional modules

Fan motor
Provides the required airflow and pressure difference.
Prefilter
Captures larger particles and protects the downstream filter.
High-efficiency filter and seals
Capture particles and limit bypass leakage.
Housing and controls
Distribute airflow and regulate fan operation.