ENGINEERING GUIDE
Selection and design guide
Rectifies the AC supply into a DC bus and inverts it to drive the servo motor, with current, speed and position control loops inside. To select, choose the motor first and match the drive by current, set the command interface and electronic gear, decide whether an external regenerative resistor is needed, and after installation do inertia identification, gain tuning and notch filtering.
01Construction and how it works
The main circuit of a servo drive is rectifier → DC bus → inverter: the AC supply is rectified and filtered into a DC bus, and an IGBT inverter bridge outputs three-phase current to the motor using SVPWM (space vector pulse width modulation) (both the Delta ASDA-B2 and Leadshine L6N specification tables state SVPWM control). When the motor decelerates or is pulled down by a heavy load it becomes a generator, energy flows back into the bus and bus voltage rises; above a threshold the braking circuit dumps the energy into a regenerative resistor to be burned off.
The control part is three nested loops: the innermost current loop controls torque, the middle speed loop controls speed, and the outer position loop compares commanded position with encoder feedback, multiplying the error by the position gain to give the speed command. The faster the inner loops, the stiffer the outer loop can be tuned, so speed loop bandwidth is one of a drive's performance figures (Leadshine L8S series rated 3.5 kHz speed loop bandwidth, Delta ASDA-B2 rated up to 550 Hz speed control bandwidth; the two makers measure differently, so they cannot be compared directly). Part 23 of the Mechanical Design Handbook sums it up: a servo controller controls the motor in three ways, position, speed and torque, and its accuracy determines the accuracy of the whole servo system.
Leadshine L7EC-100S~1000S (EtherCAT bus type) connection to peripheral devices: single-phase 220 VAC supply → wiring circuit breaker (trips on overcurrent) → noise filter (prevents interference from the supply line) → magnetic contactor (switches servo power on/off) → drive L1C/L2C (control power) and L1/L2 (main power); regenerative braking resistor connected between P+ and Br; 24 VDC brake supply used when the motor has a brake; U/V/W/PE are the servo motor main circuit cable, PE the motor ground; CN2 encoder cable, CN3/CN4 EtherCAT in and out, CN1 I/O cable, CN5 divided pulse output, CN6 STO interface, Type-C port to PC commissioning softwareImage source: Leadshine, AC Servo Systems General Catalogue (September 2026)
Leadshine L7P-S: RS485 communication, 16 built-in position commands
Simple point-to-point positioning
From Delta ASDA-B2 Series catalogue Specifications and the Leadshine AC Servo Systems General Catalogue L6N-S and L7P-S specification pages.
There are three control modes: position, speed and torque. Positioning axes on custom machines use position mode; screwdriving, winding/unwinding and press-fit pressure holding use torque mode; conveyor rollers and spindles use speed mode. Chapter 6 of the Inovance selection manual gives selection examples for both position and speed control; the method is the same, with position control adding a check of the electronic gear and droop pulses.
Current steps of 220 V drives (Leadshine L6N-S series example)
Rated power
Rated output current Arms
Maximum output current Arms
Regenerative resistor
100 W
1.2
4.8
None built in, external possible
400 W
3.5
9.5
None built in, external possible
750 W
5.5
16.6
Built in
1000 W
7.0
21.0
Built in
1500 W
9.5
31.1
Built in
2000 W
12
36.0
Built in
From Leadshine AC Servo Systems General Catalogue, L6N-S series specifications: only 750 W and above have a built-in regenerative resistor as standard, and all sizes can take an external one. Resistance and power of built-in resistors per the catalogue.
03Key parameters
Parameters to check when choosing a drive
Parameter
Meaning
Values and effect
Rated / maximum output current
Current available continuously and briefly
At least the motor's rated and maximum current, or peak torque cannot be used
Main circuit supply
Single or three phase, voltage class
Delta ASDA-B2 1.5 kW and below can use single-phase 200 to 255 VAC, 2 kW and 3 kW three phase only
Regenerative resistor
Resistance, power and processing capacity of the built-in resistor
See the method in "Selection steps"
Applicable load inertia
Range of load inertia the drive can tune stably
Leadshine L6N-S: less than 30 times motor inertia
Operating temperature
Leadshine L6N-S: 0 to 55 °C
Derate above 45 °C
Altitude, vibration
Leadshine L6N-S: below 1000 m; vibration less than 0.5 g (10 to 60 Hz)
Derate per the catalogue beyond these
Notch filters
Suppress mechanical resonance
Leadshine L6N-S: 3 sets, 50 to 4000 Hz; some series 4 sets, 50 to 8000 Hz
Dynamic braking
Shorts the motor windings to dissipate energy and stop on fault or sudden power loss
Built into Leadshine L6N-S; absent on some economy models
STO
Safe torque off interface
Leadshine L6N only on FS versions, standard on L7EC-S; the FESTO CMMS-AS listed in the handbook conforms to EN 61800-5-2
From Leadshine AC Servo Systems General Catalogue L6N-S and L7EC-S specifications, Delta ASDA-B2 Series catalogue, and Mechanical Design Handbook 23-488.
Leadshine L7EC-S drive interfaces: STO interface and divided pulse output at the top; on the front the display panel, Type-C commissioning port, CN1 general I/O interface (pin assignment in the table on the left: digital inputs 1 to 6, probes 1/2, digital outputs 1 to 3 positive and negative, built-in 24 V supply), EtherCAT ports and encoder interface; at the bottom the main power / regenerative resistor / motor power connector, ground terminal and encoder battery box slotImage source: Leadshine, AC Servo Systems General Catalogue (September 2026)
Position loop gain Kp and droop pulses: in position mode at constant speed, a number of pulses remain in the deviation counter, equal to the command pulse frequency divided by Kp. The larger Kp, the tighter the following, but with insufficient mechanical stiffness it oscillates. These droop pulses are worked off only when the axis stops, so Kp also sets the settling time after stopping.
ε = vs / Kp
ε
droop pulses in the deviation counter, pulse
vs
command pulse frequency, pps
Kp
position loop gain, 1/s
Inovance MS1-R Series Servo Motor Selection Manual section 6.1. Example: with vs = 25000 pps and Kp = 30 /s, ε = 833 pulse, which at 0.01 mm/pulse is a following lag of about 8.3 mm.
04Selection steps and calculation
Choose the motor first, then match the drive by currentUse the maker's motor–drive matching table (chapter 1 of the Inovance selection manual is the matching list). Drive rated and maximum currents must be at least those of the motor; encoder protocols are not interchangeable, so mixing brands is essentially not feasible.
Set interface and control modePulses from a PLC or a fieldbus; for pulses check the maximum frequency (open collector is usually only around two hundred kpps); where absolute encoders, full closed loop or gantry synchronisation are needed, confirm the drive supports them.
Set electronic gear and command frequencyMake one command pulse correspond to a whole-number mechanical displacement, and check that command pulse frequency does not exceed the drive's limit.
Decide whether an external regenerative resistor is neededCheck whether the drive has a built-in resistor and how many watts it can handle, then look at energy returned during deceleration and lowering.
Safety circuitEmergency stop via STO plus contactor; for vertical axes match the brake output to the enable timing.
(PB / ΔL) × (B / A) = N_enc
PB
mechanical displacement per motor revolution (ballscrew lead), mm
ΔL
desired displacement per command pulse (position detection unit), mm/pulse
B/A
electronic gear ratio (numerator/denominator)
N_enc
encoder pulses per revolution
Inovance selection manual section 6.1. Example: lead 5 mm, required stopping accuracy ±0.01 mm, take ΔL = 0.01 mm/pulse, 500 command pulses per revolution; a 26-bit encoder gives 67108864 pulses per revolution, so B/A = 67108864/500. The Delta ASDA-B2 permitted electronic gear ratio is 1/50 < N/M < 25600 (catalogue text). The electronic gear changes only the command unit, not mechanical accuracy.
vs = 1000·VL / (60·ΔL)
vs
command pulse frequency, pps
VL
load speed, m/min
ΔL
position detection unit, mm/pulse
Inovance selection manual section 6.1: with VL = 15 m/min and ΔL = 0.01 mm, vs = 25000 pps. Under pulse control, vs must be below the limits of both controller output and drive input.
When a regenerative resistor is needed: decide in the three steps below.
Check the drive's built-in capacitySmall drives often have no built-in resistor (Delta ASDA-B2 100 W and 200 W do not; Leadshine L6N-S below 750 W do not). Where there is one, the catalogue gives its processing capacity, such as 30 W for the Delta ASDA-B2 0.4 to 1.5 kW built-in resistor and 50 W for 2 to 3 kW.
Calculate energy returned per decelerationUse the kinetic energy formula below to work out the energy released as motor and load decelerate from running speed to zero, which after friction losses enters the bus; on vertical axes the potential energy of the load is also returned when lowering, often far more than the kinetic energy. Multiplied by decelerations per minute, this gives average regenerative power.
If exceeded, add an external resistor or change operating conditions firstInovance's order of measures: reduce the torque limit, lengthen deceleration time, lower maximum speed, and if the alarm persists add an external braking resistor; even with a built-in resistor, under some regenerative conditions the energy still exceeds its permissible loss and an external one is needed.
Ep = Jeq·(ω1² − ω0²) / 2
Ep
kinetic energy released by rotating masses during deceleration, J
Jeq
total inertia referred to the motor shaft (motor + load), kg·m²
ω1, ω0
angular speed at start and end of deceleration, rad/s, ω0 = 0 for a full stop
Mechanical Design Handbook table 7-4-2 (braking torque calculation, load torque term for horizontal braking). Used to estimate the upper limit of returned energy; what actually enters the bus is less after friction and motor copper losses.
Built-in regenerative resistors and minimum permissible resistance (Delta ASDA-B2 example)
Drive kW
Built-in resistance
Built-in resistor power
Built-in processing capacity
Minimum permissible resistance
0.1, 0.2
—
—
—
60 Ω
0.4, 0.75
100 Ω
60 W
30 W
60 Ω
1.0, 1.5
40 Ω
60 W
30 W
30 Ω
2.0, 3.0
20 Ω
100 W
50 W
15 Ω
From Delta ASDA-B2 Series catalogue, Selection of Regenerative Resistor. On ALE05 regeneration error, increase resistor capacity or reduce resistance, but never below the minimum permissible resistance; with several resistors in parallel the total must also not be below it. For other brands follow their manuals.
Inertia identificationJog with no load or with load so the drive learns the load inertia ratio.
Choose stiffness level, auto-tuneThe Leadshine L6N has one-key auto-tuning and stiffness parameters; start at low stiffness and step up, backing off one or two levels when vibration or squealing appears.
Suppress resonanceFind the resonance frequency from the speed waveform or spectrum and set a notch filter; for timing belts and long cantilever tip sway use vibration suppression.
Add feedforward to shorten settlingSpeed feedforward reduces following lag; too much causes overshoot.
Export parameters for the recordImport them directly when replacing the drive.
L7EC-100S~1000S between P+ and Br; 1.5 kW and above between P+ and B2, removing the B1/B2 jumper
Leadshine connection diagram
Brake supply
Separate 24 VDC supply; the drive's built-in 24 V supply must not be used for the motor brake
Leadshine wiring diagram
Fieldbus
Cat 5e double-shielded network cable
Leadshine wiring note 1
Encoder divided output
Twisted shielded cable, shield connected to PE at both ends, GND reliably connected to the host signal ground
Leadshine wiring note 3
DO outputs
User-supplied 12 to 24 V, each point maximum 30 VDC, 50 mA
Leadshine wiring note 2
STO
When using STO remove the jumper and connect to the safety switch
Leadshine wiring diagram
Motor ground
The PE terminal is the motor ground terminal and must be connected
Leadshine connection diagram
Terminal names differ between brands; wire per the manual of the drive used.
Mount the drive vertically in the cabinet with ventilation space above and below; derate per the catalogue above 45 °C in the cabinet.
Route power cables, encoder cables and signal cables separately, not bundled together.
Before power-up confirm motor direction, limits and home; jog with no load before connecting the load.
Bus capacitors stay charged after power-off; wait until the indicator goes out before disconnecting wires.
06Failure modes and maintenance
Common alarms, causes and remedies
Alarm
Main causes
Remedy
Overvoltage
Deceleration too fast, large inertia ratio, vertical lowering; too much regenerative energy
Lengthen deceleration, lower maximum speed, add or enlarge the regenerative resistor
Regenerative braking error / braking rate too high
Regenerative resistor not connected, wrong resistance or power, jumper not removed
Choose the resistor per the catalogue, check the B1/B2 jumper
Undervoltage / phase loss
Insufficient supply capacity, loose wiring
Check supply and terminals
Overcurrent
U, V, W short-circuited or grounded, drive damaged
Power off and measure insulation, replace cables
Overload
RMS torque above rated, mechanical jamming, brake not released
Recalculate Trms, check mechanics and brake
Excessive position deviation
Low gain, acceleration too high, load jammed, insufficient peak torque
Raise gain or slow acceleration, check mechanics, check drive maximum current
Encoder feedback error
Cable broken, interference, low battery
Check shielding and grounding, replace cable or battery
Overheating
High cabinet temperature, failed fan
Improve ventilation, derate for temperature
Alarm types from the Leadshine L6N-S alarm function list (overvoltage, undervoltage, overcurrent, overload, overheating, overspeed, main supply phase loss, regenerative braking error, excessive position deviation, encoder feedback error, braking rate too high, travel limit exceeded, EEPROM error) and Delta ALE05; causes and remedies are a general compilation.
Maintenance: clean fans and heat sinks regularly; on multiturn absolute systems keep the drive powered while changing the battery; record parameter changes, and when problems arise compare parameters first.
07Common design mistakes
Matching the drive by power instead of current. With drive maximum current below the motor's, the motor's peak torque cannot be used and position deviation alarms occur during acceleration.
Not calculating regeneration on vertical axes. Potential energy is all returned when lowering; small drives without built-in resistors trip on overvoltage as soon as they run.
External resistor fitted without removing the jumper, or resistance below the permissible minimum. The braking transistor fails from overcurrent.
Powering the brake from the drive's built-in 24 V. Leadshine explicitly forbids this; brake current drags down the control supply.
Signal and power cables in the same trunking. Pulses are disturbed and position drifts gradually, which checking the mechanics never finds.
High speed on open-collector pulses. Delta open collector is only 200 kpps; with a fine electronic gear and high speed the pulse frequency is insufficient, so use differential or a fieldbus.
The higher the gain the better. With insufficient mechanical stiffness high gain causes squealing; do inertia identification and notch filtering first, then raise stiffness.
Emergency stop by removing servo enable only. Enable is not a safety circuit; where personnel safety is involved use STO and design to safety standards.
08Related standards and maker series
Standards cited in the sources
Standard
Subject
Source
EN 61800-5-1, UL 61800-5-1
Adjustable speed electrical power drive systems, safety requirements (electrical, thermal and energy)
Inovance selection manual chapter 7
EN 61800-3
Adjustable speed electrical power drive systems, EMC requirements
Inovance selection manual chapter 7
EN 55011
Radio disturbance limits for industrial equipment
Inovance selection manual chapter 7
EN 61800-5-2
Adjustable speed electrical power drive systems, functional safety requirements
Mechanical Design Handbook 23-488 (FESTO CMMS-AS)
ISO 13849-1
Safety of machinery, safety-related parts of control systems
Mechanical Design Handbook 23-488
Use the current edition.
Inovance: SV630, SV660, SV670, SV680 series (matched to MS1-R motors by encoder).
Leadshine: L3, L5, L6, L7, L8 single-axis drives, 2L3/2L5/2L6 dual-axis, 4LF7EC/6LF7EC multi-axis, L6EC-L and L8ECL-S direct drive drives.
Delta: ASDA-B2 and other series.
FESTO: CMMS-AS (listed in part 23 of the Mechanical Design Handbook).
Delta, AC Servo Drive & Motor ASDA-B2 Series catalogue (English, 2021-10) ↗Selection of Regenerative Resistor (built-in resistor specifications, minimum permissible resistance, ALE05 handling); Specifications (supply, SVPWM, pulse types and frequency, electronic gear ratio range, analogue input, speed bandwidth); Wiring notes
Inovance, MS1-R Series Servo Motor Selection Manual B05 (Chinese) ↗Chapter 1 motor and drive matching list; section 3.5 overvoltage, overload and braking resistor when the permissible inertia ratio is exceeded; section 6.1 position control selection example (electronic gear, command pulse frequency, droop pulses in the deviation counter); chapter 7 certification standards
Mechanical Design Handbook, part 23: Pneumatics, chapter 11, 5.1 Servo motor controllersPrinted page 23-488: three control methods, CMMS-AS conforming to EN 61800-5-2 and ISO 13849-1
Mechanical Design Handbook, part 7: Shafts and their connections, chapter 4: Brakes, 2.2 Determining braking torquePrinted page 7-364: table 7-4-2 braking torque calculation (kinetic energy term of rotating masses)
Industry selection and calculation material (compiled)Servo commissioning notes: order of inertia identification, stiffness adjustment and resonance suppression
Tables and formulas are rearranged from the sources above. Verify against the current standard and the manufacturer catalogue before finalising a design. Updated 2026-11-17
ONLY ON MECHWIKI / SELECT · BUY · MAINTAIN
Buying and using: calculators, sellers, uses
The notes below cover the “Motor drives” category. MechWiki prepared these category notes from public standards and engineering references. Use the selected manufacturer’s catalog for ratings, life factors and dimensions.
TOOLS / CALCULATE
Related selection calculators
Use these calculators for a preliminary estimate, then verify the result against this entry, the manufacturer catalogue and installation limits. Results do not replace a specific model rating.
The directory links to manufacturer selection and CAD resources and identifies the maker of the pictured example. Check stock and lead time with the supplier. Price comparison and ranking are not available yet.
Representative series and official product pages; a manufacturer may offer other suitable series. Product ranges, availability and applicability are governed by manufacturer information. This is not a ranking, recommendation or equivalence judgment.
Panasonic IndustryMotors, sensors, relays and other electromechanical components.
Mitsubishi ElectricMELSERVO AC servos, including HK-KT and HG-KN motors with matching servo amplifiers, plus factory automation products such as PLCs and variable-frequency drives.